System Installation
AXP 1410 Installation and Use (6806800H70F)
57
Procedure
Have the following tools on hand before you begin these steps: standard Phillips screwdriver,
nut driver, torque wrench, multimeter, and lug kit.
1. Locate the target power input cable’s terminals at the branch circuit or power
distribution unit. Open the external circuit breakers that provide DC feed power to
the PEM.
2. Lock and tagout the circuit breakers on the branch circuit or power distribution
unit.
3. Using the appropriate tool, carefully remove the plastic covering over the terminal
blocks.
4. Confirm that there is no power to the PEM lug bolts. Using a multimeter, measure
between the two lugs and then measure between the chassis ground and each lug.
If the DC potential is 3.0VDC or less, then power is not present.
5. Attach the DC power cables (input and return) to the dual lug bolts on each PEM.
6. Using a torque wrench, tighten the nuts with a recommended torque setting of
35.5 to 38.5 inch-pounds. Make sure all DC leads are fastened securely.
7. Replace the plastic cover over the terminal blocks.
8. Verify that the circuit breakers are in the ON position.
Cables may or may not be preinstalled at the branch circuit or power distribution unit.
If the DC power cables are not connected to the branch circuit or power distribution unit,
connect the power cables to the PEMs before connecting the DC power cables to the
external power source.
If the DC power cables are connected to the branch circuit or power distribution unit, a
qualified service person must confirm that the power to the cables is terminated (off) before
continuing the steps to attach the cables to the PEMs.
In either case, use a multimeter to check the PEM end of the terminals to confirm there is no
power present.
Summary of Contents for AXP 1410
Page 12: ...AXP 1410 Installation and Use 6806800H70F 12 List of Tables ...
Page 14: ...AXP 1410 Installation and Use 6806800H70F 14 List of Figures ...
Page 22: ...AXP 1410 Installation and Use 6806800H70F About this Manual 22 About this Manual ...
Page 25: ...System Overview AXP 1410 Installation and Use 6806800H70F 25 Figure 1 2 System Rear View ...
Page 62: ...System Installation AXP 1410 Installation and Use 6806800H70F 62 ...
Page 82: ...FRU Installation AXP 1410 Installation and Use 6806800H70F 82 ...
Page 118: ...Supported IPMI Commands AXP 1410 Installation and Use 6806800H70F 118 ...
Page 164: ...FRU Information and Sensor Data Records AXP 1410 Installation and Use 6806800H70F 164 ...
Page 201: ...Index AXP 1410 Installation and Use 6806800H70F 201 ...
Page 202: ...Index AXP 1410 Installation and Use 6806800H70F 202 ...
Page 203: ......