System Installation
AXP 1410 Installation and Use (6806800H70F)
49
Observe the following general safety notes when installing your system:
z
Restricted access area - The system is only to be installed in a restricted access area.
z
Installation codes - This unit must be installed in accordance with the National Electrical
Code, Articles 110.16, 110.17, and 110.18 and the Canadian Electrical Code, Section 12.
z
Conductor ampacity - According to UL 60950, Annex NAE (NEC Article 645-5(a)), the
branch-circuit conductors supply must have an ampacity of not less than 125% of the
total connected load. Per NEC Article 310.15 and Table 310.16, the minimum American
Wire Gauge (AWG) has to be selected.
z
Overcurrent protection - A readily accessible listed branch-circuit overcurrent protective
device must be incorporated into the building wiring.
Emerson is not responsible for regulatory compliance or malfunction of any user-modified
product.
System Damage
Environmental contamination can impair system operation.
Locate the system in a stable area free of movement and free of dust, smoke, and
electrostatic discharge (ESD). Make sure, that the temperature does not exceed the
operating temperature given in the environmental requirements in this manual and allow
room for proper air cooling.
System Overheating
Improper cooling leads to blade damage.
To ensure proper cooling always operate the system in a horizontal position. Furthermore,
keep clear at least 6 cm adjacent to the cooling vents on the chassis front and back side.
Summary of Contents for AXP 1410
Page 12: ...AXP 1410 Installation and Use 6806800H70F 12 List of Tables ...
Page 14: ...AXP 1410 Installation and Use 6806800H70F 14 List of Figures ...
Page 22: ...AXP 1410 Installation and Use 6806800H70F About this Manual 22 About this Manual ...
Page 25: ...System Overview AXP 1410 Installation and Use 6806800H70F 25 Figure 1 2 System Rear View ...
Page 62: ...System Installation AXP 1410 Installation and Use 6806800H70F 62 ...
Page 82: ...FRU Installation AXP 1410 Installation and Use 6806800H70F 82 ...
Page 118: ...Supported IPMI Commands AXP 1410 Installation and Use 6806800H70F 118 ...
Page 164: ...FRU Information and Sensor Data Records AXP 1410 Installation and Use 6806800H70F 164 ...
Page 201: ...Index AXP 1410 Installation and Use 6806800H70F 201 ...
Page 202: ...Index AXP 1410 Installation and Use 6806800H70F 202 ...
Page 203: ......