Site Preparation
AXP 1410 Installation and Use (6806800H70F)
45
Fan trays are mounted in the shelf top. The figure below shows the general airflow for the
system.
The Cooling subsystem is compliant to CP-TA B.4. The cooling system provides for greater than
40 CFM for the front blade and 5.0 CFM for the RTM.
The actual cooling performance depends on the slot population and the heat sink design of
installed blades and should be validated based on the used system configuration.
The cooling subsystem is designed to provide 31.1 CFM in the front and presence of any single
cooling failure.
Figure 2-2
Shelf Airflow
RTM
Outlet Plenum
Chassis
Front
Chassis
Rear
Chassis
Exhaust
Air Flow
Lower Front Air Intake
Lower FTMs
Upper FTM
Room
Ambient
Air Flow
PEM
Exhaust
Summary of Contents for AXP 1410
Page 12: ...AXP 1410 Installation and Use 6806800H70F 12 List of Tables ...
Page 14: ...AXP 1410 Installation and Use 6806800H70F 14 List of Figures ...
Page 22: ...AXP 1410 Installation and Use 6806800H70F About this Manual 22 About this Manual ...
Page 25: ...System Overview AXP 1410 Installation and Use 6806800H70F 25 Figure 1 2 System Rear View ...
Page 62: ...System Installation AXP 1410 Installation and Use 6806800H70F 62 ...
Page 82: ...FRU Installation AXP 1410 Installation and Use 6806800H70F 82 ...
Page 118: ...Supported IPMI Commands AXP 1410 Installation and Use 6806800H70F 118 ...
Page 164: ...FRU Information and Sensor Data Records AXP 1410 Installation and Use 6806800H70F 164 ...
Page 201: ...Index AXP 1410 Installation and Use 6806800H70F 201 ...
Page 202: ...Index AXP 1410 Installation and Use 6806800H70F 202 ...
Page 203: ......