Table D-1 lists all of the configurable parameters of the transducer block,
indicating the descriptions and index numbers for each parameters.
Table D-1. Transducer Block
Parameters
Parameter
Index Number
Definition
ALERT_KEY
4
ID number of the transmitter–may be used on the host for sorting alarms
BLOCK_ALM
8
Block alarm
BLOCK_ERR
6
Reflects the error status associated with hardware or software components
associated with a block
CAL_MIN_SPAN
18
Minimum calibrated span value allowed–this minimum span information is necessary
to ensure that the two calibrated points (high and low) are not too close together
CAL_POINT_HI
16
Highest calibrated value
CAL_POINT_LO
17
Lowest calibrated value
CAL_UNIT
19
Engineering units code index for calibration values
COIL_DRIVE_CURRENT
36
Current at which the coils are being driven (500 mA)
COIL_DRIVE_FREQUENCY
35
Frequency at which the coils are being driven (5 or 37.5 Hz)
COLLECTION_DIRECTORY
12
Directory that specifies the number, starting indices, and DD item IDs of the data
collections in each transducer within a transducer block
DAMPING
30
Damping filter value (in seconds)
DENSITY_UNIT
31
Unit code associated with DENSITY_VALUE. Valid values are lb/cubic feet, or
kg/cubic meter
DENSITY_VALUE
75
User entered density value to be used by the transducer block when calculating flow
rate in mass flow units
DSP_SOFTWARE_REV_NUM
49
DSP software Rev Number–major, minor, build
FLOW_TUBE_LINE_SIZE
34
Inside diameter of flowtube (in millimeters)–see Table D-2
for supported enumerated line sizes.
LOW_FLOW_CUTOFF
37
When flow rate is less than this entered value, flow rate output will be set to 0 ft/s
MODE_BLK
5
Mode of the record of the block–contains the actual, target, permitted,
and normal modes
PRIMARY_VALUE
14
Measured value and status
PRIMARY_VALUE_RANGE
15
High and low range limit values, engineering units code, and number of digits to the
right of the decimal point to be used to display the primary value–see Table D-3.
PRIMARY_VALUE_TYPE
13
Type of measurement represented by the primary value
SENSOR_CAL_DATE
25
Date of the last sensor calibration–intended to reflect the calibration of the sensor
SENSOR_CAL_LOC
24
Location of the last sensor calibration–describes the physical location at which the
calibration was performed
SENSOR_CAL_METHOD
23
Method of the last sensor calibration–ISO defines several standard methods of
calibration (This parameter is intended to record that method or if some other method
was used.)
SENSOR_CAL_WHO
26
Name of the person responsible for the last sensor calibration
SENSOR_RANGE
21
High and low range limit values, engineering units code, and number of digits to the
right of the decimal point for the sensor–see Table D-3.
SENSOR_SN
22
The sensor serial number.
SENSOR_TYPE
20
Sensor type.
STRATEGY
3
Can be used to help group the blocks (Not checked or processed by the block)
ST_REV
1
Static Revision–incriminated when parameter changed.
TAG_DESC
2
Static tag–ASCII character string
TRANSDUCER_DIRECTORY
9
Directory that specifies the number and starting indices of the transducers in the
transducer block.
TRANSDUCER_TEMP
44
Calculated transmitter temperature with status.
TRANSDUCER_TYPE
10
Identifies the transducer.
TUBE_CAL_NO
33
Flowtube gain and zero offset number used in flow calculation
(Number entered is locate on physical tag of the flowtube.)
UPDATE_EVT
7
Update event
XD_ERROR
11
Transducer error
Summary of Contents for 8700 Series
Page 2: ......
Page 4: ......
Page 12: ...Reference Manual 00809 0100 4793 Rev CA August 2004 1 4 Rosemount 8742C ...
Page 64: ...Reference Manual 00809 0100 4793 Rev CA August 2004 5 12 Rosemount 8742C ...
Page 102: ...Reference Manual 00809 0100 4793 Rev CA August 2004 Rosemount 8742C A 32 ...
Page 116: ...Reference Manual 00809 0100 4793 Rev CA August 2004 Rosemount 8742C B 14 ...
Page 135: ......