 PROGRAMMING YOUR THERMOSTAT

 

CONTINUED FROM FIFTH PAGE

6.  Repeat steps 4 and 5 to select the start time and heating tem-

perature for the 2nd heating program period.

7.  Repeat steps 4 through 6 for the 3rd and 4th heating program 

periods. Weekday heating programs are now complete.

8.  Press PRGM once. “

SA SU” (indicating weekend program) will 

appear in the display, along with the start time for the 1st heat-
ing period and the currently programmed temperature.

9.  Repeat  steps  4  through  8  to  complete  weekend  heating  pro-

gramming.

10. When  you  have  completed  entering  your  heating  program, 

press RUN.

Enter Cooling Program

If the outside temperature is below 50°F, disconnect pow-
er to the cooling system before programming. Energizing 
the air conditioner compressor during cold weather may 
cause personal injury or property damage.

1.  Move SYSTEM switch to 

COOL position.

2.  Follow the procedure for entering your heating program, using 

your selected cooling times and temperatures.

Check Your Programming

Follow these steps to check your thermostat programming one final 
time before beginning thermostat operation.

1.  Move SYSTEM switch to 

HEAT position.

2.  Press PRGM to view the 1st weekday heating period time and 

temperature.  Each  time  you  press  PRGM,  the  next  heating 
period time and temperature will be displayed in sequence for 
weekday, then weekend program periods (you may change any 
time or temperature during this procedure).

3.  Press RUN.
4.  Move SYSTEM switch to 

COOL position.

5.  Repeat step 2 to check cooling temperatures.
6.  Press RUN to begin program operation. 

YOUR THERMOSTAT  IS  NOW  COMPLETELY  PROGRAMMED 
AND  READY  TO  AUTOMATICALLY  PROVIDE  MAXIMUM 
COMFORT AND EFFICIENCY!

7

 SPECIFICATIONS

ELECTRICAL DATA
Electrical Rating: 
 

MV to 30 VAC 50/60 Hz. or D.C. 

 

0.05 to 1.0 Amps (Load per terminal) 

 

1.5 Amps Maximum Total Load (All terminals combined)

THERMAL DATA
Setpoint Temperature Range:
 

 

 

45°F to 90°F (7°C to 32°C) 

Operating Ambient Temperature Range: 
 

32°F to 105°F 

(0°C to 41°C)

 

Operating Humidity Range: 
 

0 to 90% RH (non-condensing) 

Shipping Temperature Range: 
 

-40°F to 150°F 

(-40°C to 66°C)

 

8

 TROUBLESHOOTING

Reset Operation
If  a  voltage  spike  or  static  discharge  blanks  out  the  display  or 
causes erratic thermostat operation you can reset the thermostat 
by pressing 

 , 

 and TIME at the same time. This also resets 

the  factory  defaults.  If  the  thermostat  has  power,  has  been  reset 

and  still  does  not  function  correctly  contact  your  heating/cooling 
service person or place of purchase.
Batteries
For best results, replace batteries once a year with new premium 
brand alkaline batteries such as Duracell

® 

or Energizer

®

Symptom

Possible Cause

Corrective Action

Heat, Cool or Fan Runs 
Constantly. 

Blown fuse or tripped circuit breaker.  

1. 

Furnace power switch to OFF.      

2. 

Furnace blower compartment door or 

3. 

panel loose or not properly installed.   

Replace fuse or reset breaker.
Turn switch to ON.
Replace door panel in proper position to engage safety 
interlock or door switch.  

 

No Heat

Pilot light not lit.  

1. 

SYSTEM Switch not set to HEAT. 

2. 

Loose connection to thermostat or 

3. 

system.
Furnace Lock-Out Condition. Heat may 

4. 

also be intermittent.

Re-light pilot.
Set SYSTEM Switch to 

HEAT and raise setpoint 

temperature above room temperature. 
Verify thermostat and system wires are securely 
attached.
Many furnaces have safety devices that shutdown 
when a lock-out condition occurs. If the heat works 
intermittently contact the furnace manufacturer or local 
service person for assistance.   

Summary of Contents for 1F78

Page 1: ...mostat With wires still attached remove wall plate from the wall If the old thermostat has a wall mounting plate remove the thermostat and the wall mounting plate as an assembly 4 Identify each wire attached to the old thermostat 5 Disconnect the wires from the old thermostat one at a time DO NOT LET WIRES FALL BACK INTO THE WALL 6 Install new thermostat using the following procedures PART NO 37 6...

Page 2: ...onic systems Both settings produce a very accurate temperature control and can be set to your personal preference As received the thermostat cycles the system just under 1 F With W905 clipped the system cycles at approxi mately 1 5 F Take care when securing and routing wires so they do not short to adjacent terminals or rear of thermostat Personal injury and or property damage may occur CAUTION TE...

Page 3: ...ER WIRE Reversing valve is energized when the system switch is in the HEAT position Fan Relay 5 CHECK THERMOSTAT OPERATION NOTE To prevent static discharge problems touch side of thermo stat to release static build up before touching any keys If at any time during testing your system does not operate properly contact a qualified service person Fan Operation If your system does not have a G termina...

Page 4: ...the next program period be gins Then the thermostat will automatically revert to the pro gram HOLD TEMPERATURE The thermostat can hold any tem perature within its range for an indefinite period without re verting to the programmed temperature Press HOLD button HOLD will be displayed Then choose the desired temper ature by pressing or The thermostat will hold the room temperature at the selected se...

Page 5: ...es you want during each period You may also want to look at the sample program table to get an idea of how the thermostat can be programmed 1ST 2ND 3RD 4TH 1ST 2ND 3RD 4TH SAMPLE Heating Cooling Schedule Plan Factory Program 6 00 AM 8 00 AM 5 00 PM 10 00 PM 6 00 AM 8 00 AM 5 00 PM 10 00 PM 6 00 AM 8 00 AM 5 00 PM 10 00 PM 6 00 AM 8 00 AM 5 00 PM 10 00 PM 70 F 62 F 70 F 62 F 78 F 85 F 78 F 82 F 70 ...

Page 6: ... TO AUTOMATICALLY PROVIDE MAXIMUM COMFORT AND EFFICIENCY 7 SPECIFICATIONS ELECTRICAL DATA Electrical Rating MV to 30 VAC 50 60 Hz or D C 0 05 to 1 0 Amps Load per terminal 1 5 Amps Maximum Total Load All terminals combined THERMAL DATA Setpoint Temperature Range 45 F to 90 F 7 C to 32 C Operating Ambient Temperature Range 32 F to 105 F 0 C to 41 C Operating Humidity Range 0 to 90 RH non condensing...

Page 7: ...to test the Heat Cool system for correct operation If the system operates correctly replace the thermostat Furnace Cycles Too Fast or Too Slow narrow or wide temperature swing The location of the thermostat and or 1 the size of the Heating System may be influencing the cycle rate Digital thermostats normally provide precise temperature control and may cycle faster than some older mechanical models...

Page 8: ...White Rodgers is a division of Emerson Electric Co The Emerson logo is a trademark and service mark of Emerson Electric Co Homeowner Help Line 1 800 284 2925 www white rodgers com www emersonclimate com ...

Page 9: ... com www emersonclimate com LÍNEA DE AYUDA PARA EL USUARIO 1 800 284 2925 White Rodgers es una división de Emerson Electric Co El logotipo de Emerson es una marca comercial y una marca de servicio de Emerson Electric Co ...

Page 10: ...ncionando correctamente Si el sistema funciona correctamente cambie el termostato Los ciclos de la caldera son 1 La ubicación del termostato y o el tamaño del Normalmente los termostatos digitales proporcionan un demasiado cortos o demasiado sistema de calefacción pueden influir en la control preciso de la temperatura y pueden apagarse y largos oscilación reducida o duración de los ciclos encender...

Page 11: ... AUTOMÁTICA EL MÁXIMO CONFORT Y EFICIENCIA 7 ESPECIFICACIONES DATOS ELÉCTRICOS Características eléctricas MV a 30 VCA 50 60 Hz o CC 05 a 1 0 amps carga por terminal Carga total máxima 1 5 amps todas las terminales combinadas DATOS TÉRMICOS Rango de temperaturas de referencia 45 F a 90 F 7 C a 32 C Temperatura ambiente operativa 32 F a 105 F 0ºC a 41ºC Humedad operativa 0 a 90 HR sin condensación T...

Page 12: ...igeración para el programa semanal Utilice la tabla que se encuentra al pie de la página para planificar las horas y temperaturas de programación que desea durante cada período También puede consultar la tabla de ejemplos de programas para tener una idea de cómo programar el termostato 1 2 3 4 1 2 3 4 EJEMPLO Plan de programación de calefacción refrigeración programa de fábrica 6 00 AM 8 00 AM 5 0...

Page 13: ...a MANTENER TEMPERATURA El termostato puede mantener cual quier temperatura dentro de su rango por un tiempo indefinido sin volver a la temperatura programada Presione el botón HOLD Apare cerá HOLD en la pantalla Luego elija la temperatura deseada pre sionando o El termostato mantendrá la temperatura am biente al valor seleccionado hasta que presione el botón RUN para volver a iniciar la ejecución ...

Page 14: ...ERIFIQUE EL FUNCIONAMIENTO DEL TERMOSTATO NOTA Para evitar problemas de descarga estática toque la parte lateral del termostato para liberar la estática acumulada antes de pulsar cualquier tecla Si en algún momento durante la prueba su sistema no funciona correcta mente póngase en contacto con un servicio técnico calificado Funcionamiento del ventilador Si su sistema no tiene una conexión terminal...

Page 15: ...exacto y pueden ajustarse según su preferencia personal Tal como se envía de fábrica el termostato apaga y enciende el sistema debajo de 1 F Con el cable de puente W905 cortado el sistema se apagará y encenderá a aproximadamente 1 5 F Al fijar y pasar los cables tenga cuidado de que no hagan cortocircuito con las terminales adyacentes o en la parte trasera del termostato Podrían producirse lesione...

Page 16: ...esión o articulada b La base que se quita aflojando todos los tornillos imperdibles c La subbase de conmutación que se quita desenroscando los tornillos de montaje que la sostienen sobre la pared o la placa adaptadora 2 Apague la electricidad en la caja de fusibles principal hasta que haya finalizado la instalación Asegúrese de que la alimentación eléctrica esté desconectada 3 Retire la cubierta d...

Reviews: