Emerson Process Management GmbH & Co. OHG
2-17
2
Installation
X-STREAM XEFD
Instruction Manual
HASXEDE-IM-EX
07/2017
**)
Configuration of relay output
terminals as per standard factory
setting (NAMUR status signals).
NAMUR status signals are auto-
matically configured Fail Safe!
Fig. 2-11: Terminals block X1 – analog signals and relay outputs 1-4
Analog Outputs
Relay Outputs 1 – 4
Terminals for analog signals and relais outputs
1 – 4 are located at the leftmost terminal module
(terminal block X1; Fig. 2-11).
2.5 Installation – Electrical
Note!
Take care of the special installation instruc-
tions in section 4.5 of the X-STREAM gas
analyzer series manual!
Analog output specification:
4 (0)–20 mA (R
B
≤
500
Ω
)
optically isolated from each other and from ana-
lyzer electronics
Specification of relay outputs 1-4:
Dry relay change-over contacts, can be used as
NO or NC.
Electrical data:
max. 30 VDC, 1 A, 30 W resistive
Pin
Signal
P2.1
Channel 1, (+) 4 (0) – 20 mA
P2.2
Channel 1, GND
P2.3
Channel 2, (+) 4 (0) – 20 mA
P2.4
Channel 2, GND
P2.5
Channel 3, (+) 4 (0) – 20 mA
P2.6
Channel 3, GND
P2.7
Channel 4, (+) 4 (0) – 20 mA
P2.8
Channel 4, GND
P2.9
Channel 5, (+) 4 (0) – 20 mA
P2.10
Channel 5, GND
P2.1
1
not used
P2.12
not used
P3.1
not used
P3.2
not used
P3.3
Output 1 (
Failure), NC
P3.4
Output 1 (
Failure), NO
P3.5
Output 1 (
Failure), COM
P3.6
Output 2 (
Maintenance Request), NC
P3.7
Output 2 (
Maintenance Request), NO
P3.8
Output 2 (
Maintenance Request), COM
P3.9
Output 3 (Out of Spec), NC
P3.10
Output 3 (Out of Spec), NO
P3.1
1
Output 3 (Out of Spec), COM
P3.12
Output 4 (
Function check), NC
P4.1
Output 4 (
Function check), NO
P4.2
Output 4 (
Function check), COM
P4.3
not used
P4.4
P4.5
P4.6
P4.7
P4.8
P4.9
P4.10
P4.1
1
P4.12
Relay Outputs
**)
Analog Outputs
Serial Interface
*)
(Index:)
/4
Name
Datum
Verant.
Bearb.
(Zeichnung Nr.; Drawing No.)
(Benennung; Description)
EWo
EWo
4.271-8120
Bez.-Schild XSTA f. XPSA 02
Label XSTA f. XPSA 02
12.12.11
12.12.11
Index
Änderung
Datum
Name
10
0m
m
30
m
m
128,00 mm
Aufkleber aus 3M SC 3698 A,
Grund silberfarbig, Druck einfarbig schwarz
und Schutzlack
Schutzpapier gekerbt
geschnitten auf Format
12 11 10 9 8 7 6 5 4 3 2 1
P2
P3
P4
ANALOG OU
T 4
ANALOG OU
T 2
ANALOG OU
T 3
ANALOG OU
T 1
GROU
ND 3
GROU
ND 1
GROU
ND 2
GROU
ND 4
K4
K3
K2
K1
X2
RS 232
RS 485 2W
RS 485 4W
M
ODBU
S
CAN
FF
9- IOIO -1
12 11 10 9 8 7 6 5 4 3 2 1 12 11 10 9 8 7 6 5 4 3 2 1
GROU
ND 5
ANALOG OU
T 5
X