CDN2000-06-25
coupling decoupling network
11/54
respect, the resulting transient voltage and current in HV busbars are characterised by a fundamental
oscillation frequency that depends on the length of the circuit and on the propagation time.
The oscillation frequency ranges from about 100 kHz to a few megahertz, depending on the influence of the
parameter mentioned above and the length of the busbars, which may vary from some tens of meters to
hundreds of meters. In this respect, the oscillation frequency of 1 MHz may considered respective of most
situations, but 100 kHz has been considered appropriate for large HV substations.
The repetition frequency is variable and a function of the distance between the switching contacts. The
minimum repetition frequency in respect of each phase, is twice the power frequency. The repetition rates
selected, 40/s and 400/s represents therefore a compromise, taking into account the different duration of
the phenomena, the suitability of the different frequencies considered and the problem related to the energy
to which the circuits under test are subjected.
Impedance of the test generator
For testing the input/output ports of measuring relays, the selection of the 200 Ohm impedance is a
compromise. This takes into account that the characteristic impedance of cables used for this purpose
(twisted pairs) has a value ranging from 120 to 150 Ohm in the frequency range above 100 kHz and for a
length of the order of 100 m.
Relevant standards:
IEC 605-4, IEC 605-22-1, IEC 61000-4-18, IEC834-1, VDE 435 Teil 303, ANSI/IEEE C37.90.1
C
S
L
Cb
Rs
Rd
U
Damped oscillatory wave
Generator
Voltage at no load
U
t
T1 = rise time 75 ns
10 to 90 %
T = oscillation period
10 µs for 0,1MHz
1 µs for 1MHz
100%
50%
Summary of Contents for CDN2000-06-25
Page 18: ...CDN2000 06 25 coupling decoupling network 18 54...
Page 22: ...CDN2000 06 25 coupling decoupling network 22 54...
Page 24: ...CDN2000 06 25 coupling decoupling network 24 54...
Page 30: ...CDN2000 06 25 coupling decoupling network 30 54...
Page 36: ...CDN2000 06 25 coupling decoupling network 36 54...
Page 38: ...CDN2000 06 25 coupling decoupling network 38 54...
Page 40: ...CDN2000 06 25 coupling decoupling network 40 54...
Page 46: ...CDN2000 06 25 coupling decoupling network 46 54 V Verification by EMC PARTNER 38...
Page 47: ...CDN2000 06 25 coupling decoupling network 47 54...
Page 49: ...CDN2000 06 25 coupling decoupling network 49 54 13 3 Assembly Instruction to MC Connectors...
Page 50: ...CDN2000 06 25 coupling decoupling network 50 54...
Page 52: ...CDN2000 06 25 coupling decoupling network 52 54...
Page 53: ...CDN2000 06 25 coupling decoupling network 53 54...
Page 54: ...CDN2000 06 25 coupling decoupling network 54 54...