5. PRIMING SETTING
P11 PRIMING SETTING
5.1 PRIMING TIME
1. Short press
▼
to access PRIME TIME setting. Default is 2 minute
2. Press “
▲
” or “
▼
“ to adjust the value.
3. Short press “Mode” to save setting or press “Speed 3” to cancel.
”
”
5.2 PRIME SPEED
1
.
Short press “
” to access
PRIME SPEED
setting
2. Press “
▲
” or “
” to adjust the value
3. Short press “Mode” to save setting or press “Speed 3” for cancel
▼
▼
5.3 PRIMING ENABLE / DISABLE
1. Short press “
” to access enable and disable setting. Default is ON
2. Press “
▲
” “
to set ON or OFF.
3. Short press “Mode” to save setting or press “Speed 3” for cancel
▼
▼”
RS485 SETTING P12
6. RS485 SETTING
The pump equipped with RS485 communication interface for external automation controller. It is not for
domestic user access purpose. It is an always ready to interface for external automation control.
The pin assignment is 1 = A and 2=B. The waterproof connector type is SP1310 4pins. SPV's RS485 is a pure
data communication without 5V power supply output.
Contact your dealer for MODBUS programing manual, if you are a system integrator
6.1 SLAVE ADDRESS
There are two parameter can be change.
1. Short press “
▼
” to access Slave Address setting. Default Is 2
(1.1) Press
▲
to adjust the value.
(1.2) Short press “Mode” to save setting or press “Speed 3” for cancel
▼
6.2 BAUD RATE
1. Short press “
” to access Baud rate Setting. Default is 9600 bp
(1.1 ) Press
▲
to adjust the value.
(1.2 )Short press “Mode” to save setting or press “Speed 3” for cancel
2. Short press “” to check the firmware version
▼
▼