OPERATION PROCEDURE    P10

1. Press “

” or “

” to turn it ON  or OFF

2. Short press “Mode” to save setting or press “Speed 3” for cancel 

3. Short press “

” or “

” to 

setting. Default speed is 2400 RPM

schedule 2 

1

Repeat the above procedure for schedule 2 setting

2. Short press “

” or “

” to schedule 3 speed setting display only. Default is 3400 RPM

4.5.1 SCHEDULE POLICY

1. Programmed Schedule Priority Schedule 1 > Schedule 2 

2. If more than 1 schedule is enables within the same time period, the controller will operate only with the 

highest priority schedule and speed. The corresponding indication light will turn on.

3.  If  all  schedules  are  completed  according  to  their  pre-set  times,  the  controller  will  return  to  the 

condition before setting the schedule.

4. When one of programmed schedules is running and before schedule end. Any operation such as Start / 

Stop,  speed  adjust  by 

  or 

,  Speed  1-3  and  any  change  by  external  RS485  MODUS.  The  schedule 

timer and speed will be resumed when it is start over by pressing the Start / Stop to run again. 

5.  The  scheduled  settings  and  auto-recover y  cannot  contradict  each  other.  When  there  is  an  error,  the 

variable  speed  driver  will  restore  the  settings  to  those  before  the  error.  (The  priority  setting  is  still 

applicable). 

P13    SYSTEM RESET TO FACTORY DEFAULT SETTING

7. SYSTEM RESET TO FACTORY DEFAULT SETTING

1. Short press “

” to access system “RESET” function

2. Press “Mode” to confirm reset to factor y default setting

8. AUTO-RECOVERY

When  there  is  an  Overcurrent,  Over voltage,  Under-voltage  or  Overheating  error,  the  system  will  recover  itself 

automatically. If two errors happen in less than a 60 seconds inter val, the auto-recover y time will increase once. If 

the auto-recover y increases by 3 times, the system will direct you to the Error menu, and will not execute the auto-

recover y. The Auto-recover y page will display the error details during the first 5 seconds and the countdown details 

during the following 5 seconds.

Press  “Start/Stop”  button  to  cancel  the  countdown  during  the  auto-recover y  process  or  to  activate  the  auto-

recover y  immediately.  (Without  activating  the  auto-run.  If  there  is  an  error  and  the  variable  speed  driver  is  in 

operation, then after the auto-recover y the system will display the auto-start page. The auto-start page will show 

the error details (same as auto-recover y, which will last for 5 seconds) and the countdown details)

Summary of Contents for SPV Series

Page 1: ...MANUAL SUPER POWER VARIABLE SPEED PUMP With Wi Fi AND MODBUS OPTIONS NSF only apply for NSF version Model SPV Series SAA STRIVE FOR CLEAR WATER www emauxgroup com EMAUX WATER TECHNOLOGY CO LTD EMPU210...

Page 2: ...mmary of Emaux Claim Process in 3 steps 1 Claim Customer contacts Emaux salesperson and provides completed details of the claim which includes 1 Information about the failed product such as the part n...

Page 3: ...erate under high pressure When any part of the circulating system i e lock ring pump filter valves etc is serviced air can enter the system and become pressurized Filter tank Lid and pre filter cover...

Page 4: ...Entrapment or entanglement hair is pulled into and or wrapped around the grate of the drain cover 4 Mechanical Entrapment the bather s jewelry or clothing gets caught in the drain or the grate 5 Evisc...

Page 5: ...ure 2 Place the pump as close to the water source as possible so that the suction pipe is short straight and direct to reduce the friction loss Don t install the pump at more than 10ft 3 meters of geo...

Page 6: ...Running speed and power rating display 3 Pre set Speed 3 pre set running speeds 4 Function settings Real time clock 3 pre set speeds 2 schedule settings NO flow self priming settings 5 Error display O...

Page 7: ...re Version Su00x Reset RESET Title Value Operation Light Start Stop Increase Page Up Decrease Page Down Mode Setting Preset Speed 1 Preset Speed 2 Preset Speed 3 Quick Setting Quick Setting Quick Sett...

Page 8: ...ble and disable switch at the end of each setting to turn it ON or OFF 5 Freeze protection default temperature is 4 degree C in 4 or 8 hours running in setting speed 6 To do any change touch save to s...

Page 9: ...ect connection is a ONE To ONE connection without access Home Network It is just like a private controller It can be connected and control by mobile phone tablet PC laptop top or any Wi Fi enable devi...

Page 10: ...r details and all lights will start flashing Press Run shortly at the error menu to auto recover the variable speed driver keep the driver Off 10 ERRORS DESCRIPTION 10 1 COMMUNICATION ERROR If the com...

Page 11: ...other When there is an error the variable speed driver will restore the settings to those before the error The priority setting is still applicable P13 SYSTEM RESET TO FACTORY DEFAULT SETTING 7 SYSTE...

Page 12: ...ation interface for external automation controller It is not for domestic user access purpose It is an always ready to interface for external automation control The pin assignment is 1 A and 2 B The w...

Reviews: