6
Description
Sensor Vari KNX 3L-TH-D
• Version: 08.12.2016 • Technical changes and errors excepted.
Configuration is made using the KNX software ETS. The
product file
can be down-
loaded from the Elsner Elektronik website on
www.elsner-elektronik.de
in the “Ser-
vice” menu.
1.0.1. Scope of delivery
•
Sensor
•
Stainless steel installation band for pole installation
•
4×50 mm stainless steel Roundhead screws and 6×30 mm dowels for wall
mounting. Use fixing materials that are suitable for the base!
1.1. Technical specification
Housing
Plastic
Colour
White / Translucent
Assembly
Surface mount
Protection category
IP 44
Dimensions
approx. 65 × 80 × 30 (W × H × D, mm)
Weight
approx. 60 g
Ambient temperature
Operation -25°…+80°C, Storage -40°…+85°C,
avoid condensation
Operating voltage
KNX bus voltage
Bus current
max. 20 mA
Data output
KNX +/- bus connector terminal
BCU type
Integrated microcontroller
PEI type
0
Group addresses
max. 2000
Assignments
max. 2000
Communication objects:
455
Temperature sensor:
Measurement range
-25°C … +80°C
Resolution
0.1°C
Accuracy
±0,8°C at -25...-10°C
±0,5°C at -10...+65°C
±0,6°C at +65...+80°C
Humidity sensor:
Measurement range
0% RH … 100% RH
Resolution
0.1% RH
Accuracy
±7,5% RH at 0...10% RH
±4,5% RH at 10...90% RH
±7,5% RH at 90...100% RH
Pressure sensor:
Measurement range
300 mbar … 1100 mbar
Summary of Contents for Vari KNX 3L-TH-D
Page 5: ...4 Clarification of signs ...