Parameter setting
Sensor Vari KNX 3L-TH-D
• Status: 19.10.2016 • Errors excepted. Subject to technical changes.
The behaviour of the switching output on release is dependent on the value of the pa-
rameter "Switching output sends" (see "Switching output")
6.11. Absolute humidity
The absolute humidity value for the air is detected from the
Vari KNX 3L-TH-D
and
can be output to the bus.
6.12. Comfort field
The
Sensor Vari KNX 3L-TH-D
can send a message to the bus if the limits of the com-
fort field are exceeded. In this way, it is for example possible to monitor compliance
with DIN 1946 (standard values) or even to define your own comfort field.
Behaviour of the switching output
On block
• Do not send message
• send 0
• send 1
On release
(with 2 seconds release delay)
[Dependent on the "Switching output
sends" setting]
Switching output sends on change
• Do not send message
• Send switching output status
Switching output sends on change to 1
• Do not send message
• if switching output = 1
send 1
Switching output sends on change to 0
• Do not send message
• if switching output = 0
send 0
Switching output sends on change and
periodically
Send switching output status
Switching output sends on change to 1
and periodically
if switching output = 1
send 1
Switching output sends on change to 0
and periodically
if switching output = 0
send 0
Use measured values
No • Yes
Sending pattern
• never
• periodically
• on change
• on change and periodically
At and above change of
(if sent on change)
0.1 g • 0.2 g • 0.5 g • 1.0 g • 2.0 g • 5.0 g
Send cycle
(if sent periodically)
5 s • 10 s • 30 s… • 2 h
Use comfort field
No • Yes