Parameter setting
Sensor Vari KNX 3L-TH-D
• Status: 19.10.2016 • Errors excepted. Subject to technical changes.
Eco setpoint
Eco mode is usually used for night mode.
If setpoint values are entered separately:
A starting setpoint value is defined as well as a temperature range in which the setpoint
value may be changed.
If the comfort setpoint value is used as a basis:
If the comfort setpoint value is used as a basis, the deviation from this value is set.
Setpoint values for frost/heat protection (building protection)
The building protection mode is used during longer absences. Setpoints for frost pro-
tection (heating) and heat protection (cooling) are determined which may not be mo-
dified from outside (no access via operating devices etc.). The building protection
mode may be activated with delay, which allows you to leave the building before the
controls switch to frost/heat protection mode.
General control variables
This setting appears for the control types "Heating
and
Cooling" only. Here, you can
decide whether to use a common control variable for heating and cooling. If the 2nd
level has a common control variable, you also determine the control mode of the 2nd
level here.
Reduce heating setpoint (in 0.1°C)
(for heating)
0…200; 30
Increase cooling setpoint (in 0.1°C)
(for cooling)
0…200; 30
Starting heating/cooling setpoint (in 0.1 °C)
valid until first communication
-300…800; 210
Min. object value heating/cooling
(in 0.1 °C)
-300…800; 160
Max. object value heating/cooling
(in 0.1 °C)
-300…800; 280
Reduce heating setpoint (in 0.1°C)
(for heating)
0…200; 50
Increase cooling setpoint (in 0.1°C)
(for cooling)
0…200; 60
Setpoint frost protection (in 0.1°C)
-300…800; 70
Activation delay
less than • 5 s • ... • 5 min • … • 2 h
Setpoint heat protection (in 0.1°C)
-300…800; 350
Activation delay
less than • 5 s • ... • 5 min • … • 2 h