![Elsner Vari KNX 3L-TH-D Installation And Adjustment Download Page 55](http://html.mh-extra.com/html/elsner/vari-knx-3l-th-d/vari-knx-3l-th-d_installation-and-adjustment_2396528055.webp)
54
Parameter setting
Sensor Vari KNX 3L-TH-D
• Status: 19.10.2016 • Errors excepted. Subject to technical changes.
Block
If necessary, activate the switching output block and set what a 1 or 0 at the block entry
means and what happens in the event of a block.
The behaviour of the switching output on release is dependent on the value of the pa-
rameter "Switching output sends" (see "Switching output")
Delays can be set via objects
(in seconds)
No • Yes
Delay from 0 to 1
none • 1 s … 2 h
Delay from 1 to 0
none • 1 s … 2 h
Switching output sends
• on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically
Cycle
(if sent periodically)
5 s ... 2 h
Use switching output block
No • Yes
Analysis of the blocking object
• At value 1: block | At value 0: release
• At value 0: block | At value 1: release
Blocking object value before first call
0 • 1
Action when locking
• Do not send message
• send 0
• send 1
Action upon release
(with 2 seconds release delay)
[Dependent on the "Switching output
sends" setting]
Switching output sends on change
do not send message •
Status object/s send/s
Switching output sends on change to 1
do not send message •
If switching output = 1
send 1
Switching output sends on change to 0
do not send message •
If switching output = 0
send 0
Switching output sends on change and
periodically
Send switching output status
Switching output sends on change to 1 and
periodically
If switching output = 1
send 1
Switching output sends on change to 0 and
periodically
If switching output = 0
send 0