![Elsner Vari KNX 3L-TH-D Installation And Adjustment Download Page 16](http://html.mh-extra.com/html/elsner/vari-knx-3l-th-d/vari-knx-3l-th-d_installation-and-adjustment_2396528016.webp)
15
Transfer protocol
Sensor Vari KNX 3L-TH-D
• Status: 19.10.2016 • Errors excepted. Subject to technical changes.
5.
Transfer protocol
Units:
Temperatures in degrees Celsius
Brightness in Lux
Air pressure in Pascal
Air humidity in %
Absolute air humidity in g/kg and/or g/m
3
Variables in %
5.1.
List of all communication objects
Abbreviation flags:
C
Communication
R
Read
W Write
T
Transfer
U
Update
No.
Text
Func-
tion
Flags
DPT type
Size
1
Software version
Output
R-CT
[217.1] DPT_Ver-
sion
2 bytes
21
Signal LED object 1s cycle
Input
-WC-
[1.1] DPT_Switch
1 bit
22
Signal LED object 4s cycle
Input
-WC-
[1.1] DPT_Switch
1 bit
41
Temperature sensor: Malfunction
Output
R-CT
[1.1] DPT_Switch
1 bit
42
Temperature sensor: External
measurement
Input
-WCT
[9.1] DPT_Val-
ue_Temp
2 bytes
43
Temperature sensor: Measured value Output
R-CT
[9.1] DPT_Val-
ue_Temp
2 bytes
44
Temperature sensor: Total
measurement
Output
R-CT
[9.1] DPT_Val-
ue_Temp
2 bytes
45
Temperature sensor: Min./Max.
measurement query
Input
-WC-
[1.017] DPT_Trig-
ger
1 bit
46
Temperature sensor: Minimum
measurement
Output
R-CT
[9.1] DPT_Val-
ue_Temp
2 bytes
47
Temperature sensor: Maximum
measurement
Output
R-CT
[9.1] DPT_Val-
ue_Temp
2 bytes
48
Temperature sensor: Min./Max.
measurement reset
Input
-WC-
[1.017] DPT_Trig-
ger
1 bit
51
Temp. threshold value 1: Absolute
value
Input/
Output
RWCT [9.1] DPT_Val-
ue_Temp
2 bytes
52
Temp. threshold value 1: (1:+ | 0:-)
Input
-WC-
[1.1] DPT_Switch
1 bit
Summary of Contents for Vari KNX 3L-TH-D