Parameter setting
Sensor Vari KNX 3L-TH-D
• Status: 19.10.2016 • Errors excepted. Subject to technical changes.
Threshold value setting using a communication object:
Define, how the threshold value is tol be received from the bus. Basically, a new value
can be received, or simply a command to increase or decrease.
During initial commissioning, a threshold value must be defined, which will be valid
until the first communication with a new threshold value. For units which have already
been taken into service, the last communicated threshold value can be used. Basically,
a humidity range is specified in which the threshold value can be changed (object value
limit).
A set threshold value will be retained until a new value or a change is transferred. The
current value is saved in EEPROM, so that it is retained in the event of a power supply
failure and will be available once the power supply is restored.
Set the
hysteresis
independent of the type of threshold value specification.
Switching output
Set the behaviour of the switching output when a threshold value is exceeded/under-
cut. The output switching delay can be set using objects or directly as a parameter.
Threshold value setting using
Parameter •
Communication objects
Starting threshold value in 0.1% RH
valid until first communication
1 … 1000; 650
Object value limit (min.)
in 0.1%RH
1…1000
Object value limit (max.)
in 0.1%RH
1…1000
Type of threshold value change
Absolute value • Increase/decrease
Increment
(upon increase/decrease change)
0.1% RH • ... • 2.0% RH • ... • 20.0% RH
Hysteresis setting
in % • absolute
Hysteresis in 0.1% RH
0...1000; 100
Hysteresis in %
(relative to the threshold value)
0 … 50; 20
When the following conditions apply, the
output is
(TV = Threshold value)
• TV above = 1 | TV - hyst. below = 0
• TV above = 0 | TV - hyst. below = 1
• TV below = 1 |TV + hyst. above = 0
• TV below = 0 |TV + hyst. above = 1
Delays can be set via objects
(in seconds)
No • Yes
Switching delay from 0 to 1
(If delay can be set via objects:
valid until 1st communication)
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
Switching delay from 1 to 0
(If delay can be set via objects:
valid until 1st communication)
None • 1 s • 2 s • 5 s • 10 s • … • 2 h