Set, in which cases threshold values received are to be kept per object.
This setting also affects the release objects of the facade automation (opening time,
outdoor temperature block, time and night closing, heat protection, pyranometer, rain
automation, indoor temperature block and solar protection automation).
Please note that the setting "After power restoration and programming" should not be
used for the initial start-up, as the factory settings are always used until the first call
(setting via objects is ignored).
Priorities
The functions of the façade are arranged according to their priorities. First named have
higher priority. 1. Wind, 2. Frost, 3. Rain.
Wind alarm
Wind threshold values that have been exceeded can trigger an alarm, i.e. the shade is
retracted and a wind extension block is activated, i.e. the shade will no longer be ex-
tended (not even by manual commands).
If the wind alarm is used, then, as a precaution, the alarm is activated, if over a period
of 48 hours no change in the measured value has been recorded at the relevant wind
sensor.
Set with what the wind alarm and, if desired, wind extension blocking is to be defined.
If
alarm or extension block per bit object
is defined, no further settings are re-
quired. The duration of blocking by the automation after a wind alarm is set in the
"façades" menu (see
Wind and rain alarm
, Seite 89).
If
Alarm or extension block per threshold value
is defined, then set which sensors
are relevant for this. The wind value measured internally in the device can be used, but
Maintain the
target threshold values received via com-
munication objects
• never
• after power supply restoration
• after power supply restoration and
programming
(applicable for façade safety and façade automation)
Use
• No
• as wind alarm per threshold value
• as wind alarm per bit object
• as wind alarm and extension block
per threshold value
• as wind alarm per threshold value/exten-
sion block per bit object
• as wind alarm per bit object/extension
block per threshold value
• as wind alarm/wind extension block
per bit object