Parameter setting
Weather Station Suntracer KNX sl
• Version: 14.07.2016 • Technical changes and errors excepted.
If necessary, activate the block for the summer compensation and set what a 1 or 0 at
the block input means and what happens in the event of a block.
6.17. Optimal usage of façade controller
functions
6.17.1. Classifying the façades for the control unit
The control options for shades are façade-related functions.
on change of
(if sent on change)
0.1°C • 0.2°C • 0.5°C • 1°C • 2°C • 5°C
Send cycle
(if sent periodically)
5 s ... 2 h; 1 min
Use block
No • Yes
Analysis of the blocking object
• At value 1: block | At value 0: release
• At value 0: block | At value 1: release
Blocking object value before first call
0 • 1
Action when locking
• do not send
• Send value
Value (in increments of 0.1°C)
(if a value is sent during blocking)
0 ... 500; 200
Fig. 18
Most buildings have 4 façades. It is gener-
ally recommended that the solar protec-
tion of each façade be controlled separate-
ly.
Fig. 19
Even in buildings with a U-shaped layout,
only 4 façades have to be controlled differ-
ently, as several have the same alignment.