9
Transfer protocol
Room Temperature Controller KNX eTR 101-BA2
• Version: 20.04.2021 • Technical changes and errors excepted.
42
Temp.control: Status Cool. level 2
(1=ON|0=OFF)
Output
R-CT
[1.1] DPT_Switch 1 Bit
43
Temp.control: Comfort extension
status
Input /
Output
RWCT [1.1] DPT_Switch 1 Bit
44
Temp.control: Comfort Extension
time
Input
RWCT [7.5] DPT_Time-
PeriodSec
2 Bytes
45
Temp. threshold value 1: Meas-
ured value
Input
-WC-
[9.1] DPT_Val-
ue_Temp
2 Bytes
46
Temp. thresholdV 1: Absolute
value
Input /
Output
RWCT [9.1] DPT_Val-
ue_Temp
2 Bytes
47
Temp. thresholdV 1: (1:+ | 0:-)
Input
-WC-
[1.1] DPT_Switch 1 Bit
48
Temp. thresholdV 1: Switching
delay from 0 to 1
Input
-WC-
[7.5] DPT_Time-
PeriodSec
2 Bytes
49
Temp. thresholdV 1: Switching
delay from 1 to 0
Input
-WC-
[7.5] DPT_Time-
PeriodSec
2 Bytes
50
Temp. thresholdV 1: Switching
output
Output
R-CT
[1.1] DPT_Switch 1 Bit
51
Temp. thresholdV 1: Switching
output block
Input
-WC-
[1.1] DPT_Switch 1 Bit
52
Temp. threshold value 2: Meas-
ured value
Input
-WC-
[9.1] DPT_Val-
ue_Temp
2 Bytes
53
Temp. thresholdV 2: Absolute
value
Input /
Output
RWCT [9.1] DPT_Val-
ue_Temp
2 Bytes
54
Temp. thresholdV 2: (1:+ | 0:-)
Input
-WC-
[1.1] DPT_Switch 1 Bit
55
Temp. thresholdV 2: Switching
delay from 0 to 1
Input
-WC-
[7.5] DPT_Time-
PeriodSec
2 Bytes
56
Temp. thresholdV 2: Switching
delay from 1 to 0
Input
-WC-
[7.5] DPT_Time-
PeriodSec
2 Bytes
57
Temp. thresholdV 2: Switching
output
Output
R-CT
[1.1] DPT_Switch 1 Bit
58
Temp. thresholdV 2: Switching
output block
Input
-WC-
[1.1] DPT_Switch 1 Bit
59
Push button 1 long-term
Output
R-CT
[1.8] DPT_Up-
Down
1 Bit
60
Push button 1 short-term
Output
R-CT
[1.10] DPT_Start
1 Bit
61
Push button 1 switching
Output
R-CT
[1.1] DPT_Switch 1 Bit
62
Push button 1 dimming
Input /
Output
RWCT [3.7] DPT_Con-
trol_Dimming
4 Bit
63
Push button 1 encoder 8 bit
Output
R-CT
[5.10] DPT_Val-
ue_1_Ucount
1 Byte
64
Push button 1 encoder 16 bit
Output
R-CT
[9.7] DPT_Val-
ue_Humidity
2 Bytes
No
Text
Function
Flags
DPT type
Size