7
Transfer protocol
Room Temperature Controller KNX eTR 101-BA2
• Version: 20.04.2021 • Technical changes and errors excepted.
6.
Transfer protocol
Units:
Temperatures in degrees Celsius
6.1.
List of all communication objects
Abbreviation flags:
C
Communication
R
Read
W Write
T
Transfer
U
Update
No
Text
Function
Flags
DPT type
Size
0
Software version
Output
R-CT
[217.1] DPT_Ver-
sion
2 Bytes
5
LED brightness in %
Input
-WC-
[5.1] DPT_Scal-
ing
1 Byte
6
Switch LED
Input
-WC-
[1.1] DPT_Switch 1 Bit
7
Temperature sensor: malfunction
Output
R-CT
[1.1] DPT_Switch 1 Bit
8
Temperature sensor: measured
value external
Input
-WCT
[9.1] DPT_Val-
ue_Temp
2 Bytes
9
Temperature sensor: measured
value
Output
R-CT
[9.1] DPT_Val-
ue_Temp
2 Bytes
10
Temperature sensor: measured
value total
Output
R-CT
[9.1] DPT_Val-
ue_Temp
2 Bytes
11
Temperature sensor: measured
value min./max. query
Input
-WC-
[1.17] DPT_Trig-
ger
1 Bit
12
Temperature sensor: measured
value minimum
Output
R-CT
[9.1] DPT_Val-
ue_Temp
2 Bytes
13
Temperature sensor: measured
value maximum
Output
R-CT
[9.1] DPT_Val-
ue_Temp
2 Bytes
14
Temperature sensor: measured
value min./max. reset
Input
-WC-
[1.17] DPT_Trig-
ger
1 Bit
15
Temp.control: HVAC mode (prior-
ity 1)
Input
-WC-
[20.102] DPT_H-
VACMode
1 Byte
16
Temp.control: HVAC mode (prior-
ity 2)
Input
RWCT [20.102] DPT_H-
VACMode
1 Byte
17
Temp.control: Mode frost/heat
protection activt.
Input
RWCT [1.1] DPT_Switch 1 Bit
18
Temp.control: Block (1 = Blocking) Input
-WC-
[1.1] DPT_Switch 1 Bit
19
Temp.control: Current setpoint
Output
R-CT
[9.1] DPT_Val-
ue_Temp
2 Bytes