24
Setting the parameters
Room Temperature Controller KNX eTR 101-BA2
• Version: 20.04.2021 • Technical changes and errors excepted.
Block
The switching output can be blocked using an object.
Set the cases in which threshold vlaues and delay times received per object are to be
retained.
The behaviour of the switching output on release is dependent on the value of the pa-
rameter "Switching output sends" (see "Switching output")
Switching delay from 0 to 1
(if delay is adjustable via objects: valid until
1st communication)
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
Switching delay from 1 to 0
(if delay is adjustable via objects: valid until
1st communication)
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
Switching output sends
• on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically
Cycle
(is sent only if "periodically" is selected)
5 s • 10 s • 30 s… • 2 h
Use switching output block
No • Yes
Assessment of the block object
• At value 1: block | At value 0: release
• At value 0: block | At value 1: release
Blocking object value before first Commu-
nication
0 • 1
Switching output behaviour
On blocking
• Do not send message
• 0 Send
• 1 Send
On release
(with 2 second release delay)
[Dependent on the "Switching output
sends" setting]
Switching output sends on change
• Do not send message
• Send switching output status
Switching output sends on change to 1
• Do not send message
• if switching output = 1
send 1
Switching output sends on change to 0
• Do not send message
• if switching output = 0
send 0
Switching output sends on change and
periodically
Send switching output status
Switching output sends on change to 1 and
periodically
if switching output = 1
send 1
Switching output sends on change to 0 and
periodically
if switching output = 0
send 0