28
Setting the parameters
Room Temperature Controller KNX eTR 101-BA2
• Version: 20.04.2021 • Technical changes and errors excepted.
Temperature sensor
If a temperature sensor T-NTC is connected to the input, set the behaviour (malfunction
object, transmission behaviour) and mixed-value calculation here. If the measured val-
ues of the sensor should deviate from the actual temperature values (e.g. in case the
installation site is not in an ideal position), this may be offset and corrected.
7.6.2. Control modes for drive control
Behaviour on button actuation in standard control mode:
Standard:
If briefly operated, the drive will move incrementally or stops. If operated longer, the
drive will move up to the end position. The time difference between "short" and "long"
is set individually.
Scenario function
• Activate
• Activate and save
Press key for longer than (in 0.1 s)
Scenario saving
only for saving
0...50
Bus function
Temperature sensor NTC
Use malfunction object
Yes • No
Offset in 0.1°C
-50...50; 0
Use external measured value
Yes • No
Ext. Measured value portion of the total
reading
only if an external value is used
5% • ... • 50% • ... • 100%
All of the following settings then pertain to the total measured value
Send behaviour
• periodically
• on change
• on change and periodically
On change of
if transmitted on change
0.1°C • ... • 0.5°C • ... • 5.0°C
Send cycle
if transmitted periodically
5 s...2 h
short:
press and hold:
Blind
Stop/step
Up or Down
Roller Shutter
Stop
Up or Down
Awning
Stop
Retract or Extend
Window
Stop
Close or Open
Control mode
Standard