54
CHAPTER 3 - INSTALLATION AND CONNECTION
Id
Inverter Model
24
CFW080220T2024...
25
CFW080280T2024...
26
CFW080330T2024...
27
CFW080010T3848...FAZ
28
CFW080016T3848...FAZ
29
CFW080026T3848...FAZ
30
CFW080040T3848...FAZ
31
CFW080027T3848...FAZ
32
CFW080043T3848...FAZ
33
CFW080065T3848...FAZ
34
CFW080100T3848...FAZ
35
CFW080130T3848...FAZ
36
CFW080160T3848...FAZ
37
CFW080010T3848...
38
CFW080016T3848...
39
CFW080026T3848...
40
CFW080040T3848...
41
CFW080027T3848...
42
CFW080043T3848...
43
CFW080065T3848...
44
CFW080100T3848...
45
CFW080130T3848...
46
CFW080160T3848...
47
CFW080240T3848...
48
CFW080300T3848...
49
CFW080240T3848...FAZ
50
CFW080300T3848...FAZ
Input RFI Filter
B84143-B36-R110
(external filter)
B84143-B50-R110
(external filter)
B84143-B50-R110
(external filter)
FEX2-CFW08
(footprint filter)
Built-in filter
FN3258-7-45 or
B84143-B8-R110
(external filter)
FN3258-16-45 or
B84143-B25-R110
(external filter)
FN3258-16-45 or
B84143-G36-R110
(external filter)
FN3258-30-47 or
B84143-G36-R110
(external filter)
FN-3258-30-47 or
B84143-B50-R110
(external filter)
FN-3258-55-52 or
B84143-B50-R110
(external filter)
Built-in filter
Conducted Emission
Level
Category C1
Category C1
Category C2 or
Category C3
Category C1
Category C1
Category C1
Category C3
Radiated Emission
Level
Category C2
Category C2
Category C3
Category C2
Category C3
Category C3
Table 3.8 (cont.)
- Inverter models list with filters and EMC category
Observe the following notes for the models presented on table
3.8:
1) CategoryC1 drives (for conducted emission) shall be mounted
inside a metallic cabinet so that the radiated emissions stay
belowthe limits for residential applications (“first environment”)
and restricted distribution (refer to item 3.3.2).
Category C2 drives (for conducted emission) do not require
installation inside metallic cabinets. Exception: models 7 and
8, that need to be mounted inside a cabinet to pass in the
radiated emission test for second environment and
unrestricted distribution (refer to item 3.3.2). When a metallic