CAPITOLO 4 - START
ACTION
HMI DISPLAY
DESCRIPTION
Press
and use the keys
and
to set the correct
value for the motor frequency
Press the
key to save the
selected option and exit the
programming mode
Press the
key to go to the
next parameter
Press the
key and use the
keys
and
to set the
correct motor power
Press the
key to save the
selected option and exit the
programming mode
Press the
key to go to the
next parameter
Press the
key and use the
keys
and
to set the
correct motor power factor (in this
case 0.70)
Press the
key to save the
selected option and exit the
programming mode
Press the
key to go to the
next parameter
Press the
key and use the
keys
and
to authorize or
not the start of the parameter
estimate
Press the
key to start the
self-tuning routine. While the self-
tuning routine is running, the display
shows "Auto”
The running of the Self-Tuning
Routine can last until 2 minutes and
after ending display will show “rdy”
(ready), when the motor parameter
were acquired with success.
Otherwise the fault “E14” is shown.
In this case refer to note
(1)
below
Set rated motor frequency:
60 Hz (the default value is maintained)
(2)
Exit the programming mode
Rated motor power range:
0 to 15 (each value represents a power
value)
Selected rated motor power:
4 = 0.75 HP / 0.55 kW
Exit the programming mode
Motor power factor range:
0.5 to 0.99
Set motor power factor:
0.70
Exit the programming mode
Parameter estimation?
0 = No
1 = Yes
1 = Yes
Self-tuning is running
Inverter finished the self-tuning routine
and is ready for operation,
or
Running of self-tuning routine has not
been realized with success
(1)
or