41
CHAPTER 3 - INSTALLATION AND CONNECTION
3.2.5 Signal and Control
Connections
The signal connections (analog inputs/outputs) and control
connections (digital inputs and relay outputs) are made on
the XC1 connector of control board (refer to the location in
figure 3.5, item 3.2.2).
There are two configurations for the control board: standard
version (CFW-08 line) and Plus version (CFW-08 Plus line),
as shown below:
Figure 3.8
- XC1 control terminal description (standard control board - CFW-08)
Note:
NC = Normally Closed Contact, NO = Normally Open Contact.
XC1 Terminal
1
DI1
2
DI2
3
DI3
4
DI4
5
GND
6
AI1 or
DI5 or
PTC1
7
+10 V
8
GND
9
10
N.C.
11
Commom
12
N.O.
Description
Factory Default Function
Digital Input 1
General Enable
Digital Input 2
FWD / REV
Digital Input 3
Reset
Digital Input 4
Start/Stop
0 V Reference
Analog Input 1 or Digital Input 5
or PTC Input
Frequency / Speed Reference
(remote mode)
Potentiometer Reference
0 V Reference
Not Used
Relay Output 1 - N.C. Contact
No Fault (P277 = 7)
Relay 1 Common Point
Relay 1 - N.O. Contact
No Fault (P277 = 7)
Specifications
4 isolates digital inputs
- Logic NPN
Minimum high level: 10 Vdc
Maximum high level: 30 Vdc
Maximum low level: 3 Vdc
- Logic PNP
Maximum low level: 10 Vdc
Minimum high level: 21.5 Vdc
Maximum high level: 30 Vdc
Input current: -11 mA
Maximum input current: -20 mA
Not connected to PE
( 0 to10) Vdc (0 to 20) mA (4 to 20)
mA (figure 3.10)
Impedance: 100 k
(voltage input)
and 500
(current input).
- Linearity error < 0,25 %
- Maximum voltage input: 30 Vdc
For further information refer to P235
detailed parameter description
+10 Vdc, ± 5 %, capacity: 2 mA
Contact capacity:
0.5 A / 250 Vac
Relay 1
10
12
11
CCW
CW
5
k
Factory Default
Settings