CAUTION
When installing S40 inverters or smaller, use L2 inductance under the following
circumstances: mains instability; thyristor converters, loads generating strong
voltage variations at startup; power factor correction systems; mains power
exceeding 500 KVA.
When installing S50 size inverters or bigger, always install line inductance,
unless they are powered through a dedicated transformer.
Always activate a line inductance for inverter sizes greater than S50, unless the
inverter is powered via a dedicated transformer.
13.5.4.3.
2T-4T
C
LASS
,
I
NTERPHASE
I
NDUCTANCE
SIZE
INVERTER MODEL
INTERPHASE INDUCTANCE MODEL
0598 1100A IM0143504
0748
S65
0831
1400A IM0143604
NOTE
Inductance designed for 12-phase connection.
Carefully follow the application diagram.
13.5.5.
I
NDUCTANCE
R
ATINGS
13.5.5.1.
V
OLTAGE
C
LASS
:
2T
–
4T
INDUCTANCE
RATINGS
DIMENSIONS HOLE
WGT
LEAKAGE
INDUCTANCE
MODEL
INDUCTANCE
TYPE
mH A
TYPE L H P M E G mm Kg
W
IM0126004 AC
3-PHASE 2.0 11 A 120 125 75 25 67 55 5 2.9 29
IM0126044 AC
3-PHASE 1.27 17 A 120 125 75 25 67 55 5 3
48
IM0126084 AC
3-PHASE 0.70 32 B 150 130 115 50 125 75 7x14 5.5
70
IM0126124 AC
3-PHASE 0.51 43 B 150 130 115 50 125 75 7x14 6
96
IM0126144 AC
3-PHASE 0.3 68 B 180 160 150 60 150 82 7x14 9
150
IM0126164 AC
3-PHASE 0.24 92 B 180 160 150 60 150 82 7x14 9.5
183
IM0126204 AC
3-PHASE 0.16 142 B 240 210 175 80 200 107 7x14 17
272
IM0126244 AC
3-PHASE 0.09 252 B 240 210 220 80 200 122 7x14 25
342
IM0126284 AC
3-PHASE 0.061 362 C 300 260 185 100 250 116 9x24 36
407
IM0126324 AC
3-PHASE 0.054 410 C 300 260 205 100 250 116 9x24 39.5
423
IM0126364 AC
3-PHASE 0.033 662 C 300 290 235 100 250 143 9x24 53
500
IM0126404 AC
3-PHASE 0.023 945 C 300 320 240 100 250 143 9x24 67
752
IM0126444 AC
3-PHASE 0.018
1260
C 360 375 280 100 250 200 12 82 1070