SINUS K
INSTALLATION
INSTRUCTIONS
141/
191
Voltage class: 4T
Applications with a braking duty cycle of 10%
Braking Resistors
Inverter Size
Braking Unit
Quantity
Recommended
Rating (Ohm)
Power(W)
Resistor Wiring
Wire Cross-Section
Mm² (Kcmils)
0598 BU1440
2T-4T 1
1.2Ohm 64000
-
120
(250)
0748 BU1440
2T-4T 1
1.2Ohm 64000
-
120
(250)
0831
BU1440 2T-4T
1
0.8Ohm
100000
Parallel connected
120 (250)
Applications with a braking duty cycle of 20%
Braking Resistors
Applicable Resistors
Inverter
Size
Braking Unit
Quantity
Recommended
Rating (Ohm)
Power
(W)
Resistor Wiring
Resultant
Rating (Ohm)
Wire Cross-
Section
Mm² (Kcmils)
0598 BU1440
2T-4T 2
2.4
64000 parallel-connected
1.2
2*95(400)
0748 BU1440
2T-4T 2
2.4
64000 parallel-connected
1.2
2*95(400)
0831 BU1440
2T-4T 2
1.6
100000 parallel-connected
0.8
2*120(500)
Applications with a braking duty cycle of 50%
Braking Resistors
Applicable Resistors
Inverter Size
Braking Unit
Quantity
Recommended
Rating (Ohm)
Power
(W)
Resistor Wiring
Resultant
Rating (Ohm)
Wire Cross-
Section
Mm² (Kcmils)
0598 BU1440
2T-4T 4
1.2 64000
series/parallel-
connected
1.2
2*120 (250)
0748 BU1440
2T-4T 4
1.2 64000
series/parallel-
connected
1.2 2*120
(250)
0831 BU1440
2T-4T 4
0.8 100000
series/parallel-
connected
0.8 2*185(400)