INSTALLATION
SINUS K
INSTRUCTIONS
118/
191
(*) max. value to be set for the Brake Enable parameter (C68 (IFD SW) or C60 (VTC SW)). Set Brake Disable
C67 (IFD SW) or C59 (VTC SW) so as not to exceed the max. power to be dissipated by the braking resistor. Set
Brake Disable=0 and Brake enable
≠
0 not to limit the operation of the built-in braking unit.
13.1.2.2.
75
O
HM
/1300W
M
ODEL
2.5 mm
2
300
L
P
13
ø4.8
68
57
Figure 48: Overall dimensions and ratings for 75
Ω
/1300W braking resistor.
Type
L
(mm)
D
(mm)
Wgt
(g)
Degree of
Protection
Mean Power that
can be Dissipated
(W)
Max. Duration of Continuous
Operation at 380-500VCA
(s)*
75 Ohm/750W
RE3063750
195 174
500 IP33
550
2.25
(*) max. value to be set for the Brake Enable parameter (C68 (IFD SW) or C60 (VTC SW)). Set Brake Disable
C67 (IFD SW) or C59 (VTC SW) so as not to exceed the max. power to be dissipated by the braking resistor. Set
Brake Disable=0 and Brake enable
≠
0 not to limit the operation of the built-in braking unit.
Type
Wgt
(g)
Degree of
Protection
Mean Power that can
be Dissipated
(W)
Max. Duration of
Continuous Operation at
200-240VAC
(s)*
56 Ohm/350W
RE2643560
400 IP55
350
3.5
100 Ohm/350W
RE2644100
400 IP55
350
3.5