INSTALLATION
SINUS K
INSTRUCTIONS
126/
191
DANGER
Before changing jumper positions, remove voltage from the equipment and wait at
least 5 minutes.
CAUTION
Never set jumpers to a voltage value lower than the inverter supply voltage, to
avoid continuous activation of the braking unit.
13.2.2.2.
A
DJUSTING
T
RIMMERS
Depending on the jumper configuration, each trimmer allows the fine-tuning of the braking unit voltage
threshold trip.
Jumper-trimmer matching is as follows:
Jumper Function
J3
Fine-tuning of pick-up voltage through trimmer RV2
J4
Fine-tuning of pick-up voltage through trimmer RV3
J5
Fine-tuning of pick-up voltage through trimmer RV4
J6
Fine-tuning of pick-up voltage through trimmer RV5
The rated voltage for the braking unit activation and its range to be set with the 4 trimmers is stated in the table
below:
Mains voltage [Vac]
Jumper
Trimmer
Minimum
braking
voltage
[Vdc]
Rated braking
voltage [Vdc]
Maximum
braking
voltage [Vdc]
200÷240 (2T)
J4
RV2
339
364
426
380÷480 (4T)
J3
RV3
700
764
826
481÷500 (4T)
J5
RV4
730
783
861
230-500
J6
RV5
464
650
810
CAUTION!!
Max. values in the table above are theoretical values for special applications
only; their use must be authorized by Elettronica Santerno. For standard
applications, never change the factory-set rated value.
Figure 55: Positions of BU200 adjusting trimmers.
Rv2 Rv3 Rv4 Rv5