User Manual
EM303B General Purpose Inverter
138
F9-02 ones place=0
After numeric reference input changed, it can only be saved by pressing
DATA
ENTER
.
F9-02 ones place=1
After the setting value of primacy numeric frequency (F0-07) changed,
it will be saved automaticallywithoutpressing
DATA
ENTER
.
F9-02 thousands place=0
Edit the numeric reference input slowly at first, and then fast later
based on the effective lasting time of terminal UP/DOWN.
F9-02 thousands place=1
Edit the numeric reference input as per the setting UP/DOWN rate
set by F9-07 based on the effective lasting time of terminal UP/DOWN, it will be calculated
by second, and only round-up no round-off.
F9-07 UP/DOWN frequency rate:
Set the acceleration/deceleration rate of terminal
UP/DOWN frequency.
Remarks:
UP/DOWN function is only applied in stepping mode.
UP/DOWN frequency rate of keypad is a fixed rate. It is only for F0-07.
Speed Setting
8.11.3
Speed Setting Mode
No.
Function
Range
Unit Default Type
F9-03
Speed Setting
Mode
Ones place:
Integrated speed input mode
0: Primary speed setting mode
1: Auxiliary speed setting mode
2:Primary speed s auxiliary
speed setting
Tens place:
Speed setting mode under jog control
0: Jog numeric speed setting mode
1: Jog numeric speed setting mode +
primary speed setting mode
2: Jog numeric speed setting mode +
auxiliary speed setting mode
Hundreds place: Relation between
auxiliary speed and primary speed
0: Primary speed + auxiliary speed
1: Primary speed - auxiliary speed
000
〇
F9-03 ones place is for selecting integrated speed input mode.
F9-03 ones place =0
The integrated speed is only set by primary speed setting mode, and
auxiliary speed setting mode is disabled.
F9-03 ones place =1
The integrated speed is only set by auxiliary speed setting mode, and
primary speed setting mode is disabled.
F9-03 ones place =2
Select integrated speed input mode =the auxiliary speed setting (Please
pay attention to that the value is positive or negative) + primary speed setting.