Because F0-00is read only, inverter responds error message. Inverter responds data frame in
hexadecimal format
01H
86H
11H
82H
6CH
Command code is 86H in error message, the highest bit 1 of 06H. If error code detail is 11H,
it means the parameter is read only.
After responding to the error data receipt, master can revise the responding program via
resending data frame or based on the error message responded by the inverter.
12.5.6 Details of 0x08 Circuit Diagnoses and Setting
Sub-function
Code
Data Requested
Response Data
Indication of
Sub-function
0000H
#data16
The same as the data requested
Circuit Diagnosis
13.6
Description of Control Command
Control Command 1(Register Address: 4000H or 7000H)
Data
Meaning
Data
Meaning
0000H
Disabled Command
0006H
Ramp to Stop
0001H
Forward Running
0007H
Coast to Stop
0002H
Reverse Running
0008H
Fault Reset
0003H
JOG Forward
0009H
+/- Input Switch
0004H
JOG Reverse
000AH
Not Used
0005H
Slave-inverter Stops
000BH
Not Used
Control Command 2(Register Address: 4000H)
Virtual Terminals from LSB to MSB are:
X1, X2, X3, X4, X5, X6, X7, VS, VF, IS, IF, Y1, Y2, R1.
Virtual
Terminals
R1 Y2 Y1 IF IS VF
VS
X7 X6 X5 X4 X3 X2 X1
Bit
15
14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
Inverter Status 1(Register Address: 4100H)
Data
Meaning
Data
Meaning
0000H
Parameter Setting
0004H
Slave-inverter Stops
0001H
Slave-inverter Runs
0005H
JOG Stop
0002H
JOG Running
0006H
Fault Status
0003H
Running in Autotuning
0007H
Factory Check