EM303B General Purpose Inverter
58
Table 6-2 Functions of Numeric Multi-function Output Terminals
No.
Function
No.
Function
0 Inverter Runs(Enabled at Running)
17 Overload Alarming Output
1 Frequency Reach Range FAR(Enabled at running)
18 Overvoltage Stall
2 Output Frequency Detection Range FDT1(Enabled at running)
19 Current Limit
3 Output Frequency Detection Range FDT2(Enabled at running)
20
Frequency Zero Speed
Detection(Output Frequency
Detection)
4 Output Frequency Detection Range FDT1(Disabled at JOG)
21 Not Used
5 Output Frequency Detection Range FDT2(Disabled at JOG)
22 Motor 2 Enabled
6 Forward/Reverse(Enabled at Running)
23 Setting running time is up
7 Frequency Input/Output Balance (Enabled at Running)
24 Not Used
8 JOG
25 Not Used
9 Inverter Fault
26 Inverter is ready for running
10 Upper Limit Frequency Reach
27 Not Used
11 Lower Limit Frequency Reach
28 FDT1LowerBounds(Pulse)
12 Not Used
29 FDT2LowerBounds (Pulse)
13 Not Used
30
FDT1 LowerBounds(voidwhen
JOG, Pulse)
14 Analog Detection Range ADT1
31
FDT2LowerBounds(voidwhen
JOG, Pulse)
15 Analog Detection Range ADT2
32 ILP Fault
16 Analog Detection Range ADT3
Table 6-3 F2-16~F2-17 Analog Outputs Full Scales
No
.
Signal
Full Scale(100.0%)
No.
Signal
Full Scale(100.0%)
0 Output Frequency Fmax
11 IS
20mA
1 Input Frequency
Fmax
12 IF
20mA
2
Synchronous
Frequency
Fmax
13
Output torque
(actual value)
2 times motor rated
torque
3
Output torque
(absolute value)
2 times motor rated torque
14 +10V
+10V
4 Not Used
15 PID Input
PID Maximum Scale
5 Not Used
16 PID Feedback
PID Maximum Scale
6 Output Current
2 times inverter rated current
17 Not Used
7 Output Voltage
1.5 times inverter rated voltage 18 Not Used
8 VP
5.00V
19 DC Bus Voltage
1.5 times rated input
voltage
9 VS
10.00V
20 Output Power
inverter rated power
10 VF
10.00V
21
Estimated frequency
/Output torque
Fmax/motor rated torque