User Manual
EM303B General Purpose Inverter
60
6.2.5
F4 Group: General Parameters of PID
No.
Function
Range
Unit Default Type S/N
F4-00
PID Regular Setting
Mode
0: Numeric PID Setting
1: VS
2: IS
3: VF
4: IF
5: VP
0
〇
128
F4-01
PID Numeric Setting 0.0~PIDMaximum Scale
V
0.0
●
129
F4-02
PID Feedback
Options
0: VF
1: IF
2: VS
3: IS
0
〇
130
F4-03
PID Maximum Scale 0.1~6000.0
10.0
●
131
F4-04
Positive/Negative
Options of PID
Upper/Lower Limit
Ones place: PID Upper Limit Options
0: Positive
1: Negative
Tens place: PID Lower Limit Options
0: Positive
1: Negative
10
●
132
F4-05
PID Regulation
Setting
0: Positive Setting
1: Negative Setting
0
〇
133
F4-06
PID Output Gain
0.00~100.00
%
100.00
●
134
F4-07
Proportional Gain GP 0.00~100.00
0.40
●
135
F4-08
Integral Time GTi
0.00~300.00 0.00
:
No integration
S
10.00
●
136
F4-09
Differential Time
GTd
0.00~100.00
mS
0.00
●
137
F4-10
Integration Function
Scale
0.00~100.00
%
100.00
●
138
F4-11
PID Upper Limit
0.00~100.00
%
100.00
●
139
F4-12
PID Lower Limit
0.00~100.00
%
0.00
●
140
F4-13
Menu Display
Control 1
Fd
FC
Fb
FA
F9
F8
F7
F6
11111111
●
141
1
1
1
1
1
1
1
1
0: No Display
,
1: Display
No.
Function
Range
Unit
Default
Type
S/N
F3-31
Parameter Copy
0: No Copy
1: Upload Parameter (From
Inverter to Keypad)
2:Download Parameter
(From Keypad to Inverter)
0
〇
127