VENTING
Element4 Gas Fireplaces
European
Home
.com
V
V2
H
V1
Distance "H" = 0 - 3m (min - max)
Distance "V1" = 500mm - 10m (min - max)
Distance "V2" = 500mm - 10m (min - max)
Distance "V" (= V1+V2) = 1m - 11m
(min - max)
Distance "V" =2x "H" (min)
Distance “H” = 0”/0.0
m
minimum to 9’10”/3.0
m
maximum
Distance “V1” = 19”/500
mm
minimum to 33’10”/10.0
m
maximum
Distance “V2” = 19”/500
mm
minimum to 33’10”/10.0
m
maximum
Distance “V” (V1+V2) = 3’3”/1.0
m
minimum to 36’/11.0
m
maximum
Distance “V” must be greater than twice the distance of “H”
Subtract 3’3”/1.0
m
of maximum height for every 90° elbow up to a maximum
of four (4) 90° elbows.
A minimum distance of 12”/304 mm between the roof and the lowest
discharge opening in the termination must be maintained.
Power vent systems are available for configurations beyond these limits.
Note: Configurations with vertical terminations may need a restrictor. See the
INSTALLING A RESTRICTOR
section, Table 6.
Figure 22
Vertical Terminations with 90° elbows
VERTICAL TERMINATIONS WITH 90° ELBOWS
12”/304
mm
minimum
VERTICAL