150 min
V
150 min
Distance "V" 1m - 11m (min - max)
26
VENTING
Element4 Gas Fireplaces
European
Home
.com
VERTICAL TERMINATIONS
When installing vertical venting with no elbows, dimension “V” must be at
least 3’3”/1.0 m minimum and no more than 36’/11.0 m maximum.
A minimum distance of 12”/304 mm between the roof and the lowest
discharge opening in the termination must be maintained.
Power vent systems are available for configurations beyond these limits.
Figure 21
Vertical Terminations with NO elbows
12”/304 mm minimum
Note: Configurations with vertical terminations may need a restrictor.
See the
INSTALLING A RESTRICTOR
section, Table 6.
12”/304
mm
minimum
VERTICAL