Piping Length, Elevation, Flare Work & Torque Settings
Model
Piping
Standard
Length
(m)
Max
Elevation
(m)
Max
Length
(m)
Additional
Refrigerant
(g/m)
GAS
LIQUID
EXH09HL1W
3/8
9.52mm
1/4
6.00mm
5
10
20
20
EXH12HL1W
3/8
9.52mm
1/4
6.00 mm
5
10
20
20
Flaring work.
Firmly hold copper pipe in a
die in the dimension shown in The table below
.
Connection Adjustment
1. Align the pipes to be connected.
2. Screw the flare nut with your
fingers,and the tighten it with
a spanner and torque wrench,
as shown in the following figure.
OUTER
DIAMETER(mm)
A(mm)
Max.
Min.
6,00
1,3
0,7
9,52
1,6
1,0
12,70
1,8
1,0
16
2,4
2,2
OUTER
DIAMETER(mm)
TIGHTENING
TORQUE(N/cm)
ADITINAL TIGHTENING
TORQUE(N/cm)
6,00
1570(160 kgf/cm)
1960(200 kgf/cm)
9,52
2940(300 kgf/cm)
3430(350 kgf/cm)
12,70
4900(500 kgf/cm)
5390(550 kgf/cm)
16
6000(611 kgf/cm)
6500(663 kgf/cm)
Caution:Excessive twisting may
break the nut,depending on the
installation conditions.