210-10 ADL
20/62
599 75 60-77
(4) Fan Mode
In fan mode, indoor fan operates at set fan speed, while compressor and outdoor fan all stop operation.
In fan mode, the temperature setting range is 16
~
30
℃
. Display is displaying operation icon and set temperature.
(5) Auto Mode
In auto mode, the system will select the operation mode (cooling, hearing of fan mode) according to the change of ambient
temperature automatically. The display displays operation icon, actual operation mode and set temperature. 30s will be delayed
for protection during mode switchover. Protection function is the same as that in other modes.
The selection method for auto operation mode in details is as below:
a.
When Tamb. ≥26
℃
, the unit operates in cooling mode. The defaulted set temperature is 25
℃
;
b. When Tamb. ≤21
℃
, the unit operates in heating mode. The defaulted set temperature is 20
℃
(if it’s the cooling only unit that
operates in fan mode, the defaulted set temperature is 25
℃
);
c. When 22
℃
≤Tamb.≤25
℃
, if the unit is turned on for the first time, it will operate in auto fan mode; if the unit is switched to auto
mode from other mode, it will keep previous operation mode; if the unit is switched to auto mode from dry mode, it will operates
in fan mode.
d. When the unit operates in auto mode, frequency of compressor during cooling and heating is same as that in cooling mode
and heating mode respectively.
Protection function:
a. It’s the same as that in cooling mode when it operates in cooling;
b.
It’s the same as that in heating ode when it operates in heating;
(6) 8
℃
Heating Function
In heating mode, press IOclock buttons on remote controller simultaneously. In this mode, “cold air prevention
protection” will be shielded.
①
8
℃
heating mode and sleep function can’t be set at the same time. If 8
℃
heating mode has been set, press sleep button will
cancel 8
℃
heating mode. The set temperature value is the set temperature before entering the 8
℃
heating mode. If sleep
function has been set, press IOclock button on remote controller simultaneously to set 8
℃
heating mode, meanwhile,
sleep function will be canceled.
②
Set temperature is 8
℃
; Indoor fan displays 8
℃
.
③
In this mode, turbo function can be set and fan speed can’t be adjusted as well.
④
In this mode, when compressor is operating, fan speed will be adjusted according to below auto fan speed; When compressor
stops operation, indoor fan operates at blowing residual heat.
When Tindoor amb. ≤9
℃
, indoor fan operates at high fan speed;
When 9
℃
<
Tindoor amb.
<
11
℃
, indoor fan operates at medium fan speed;
Whe
n Tindoor amb.≥11
℃
, indoor fan operates at low fan speed;
As for the switchover among high speed, medium speed and low speed, the unit should operate at every speed for 3minutes
and 30s at least. Others are same as that in heating mode.
⑤
The unit with memory function can memorize 8
℃
heating mode.
Summary of Contents for EXH09HL1W
Page 2: ...2010 10 ADL 2 62 599 73 60 74 ...
Page 5: ...210 10 ADL 5 62 599 75 60 77 2 ESD Requirements ...
Page 6: ...210 10 ADL 6 62 599 75 60 77 ...
Page 13: ...210 10 ADL 13 62 599 75 60 77 EXH09HL1W outdoor EXH12HL1W outdoor ...
Page 28: ...210 10 ADL 28 62 599 75 60 77 BOTTOM VIEW ...
Page 37: ...210 10 ADL 37 62 599 75 60 77 H6 Malfunction Flowchart ...