(7)SAVE Function
①
In cooling mode, if press IOclock buttons on remote controller simultaneously, the controller will enter into SAVE
mode. In SAVE mode, if press IOclock buttons on remote contr
oller simultaneously again, SAVE function won’t be set
again.
②
If remote controller is set to display set temperature, dual-
8 nixie tube display “SE”.
③
In this mode, when compressor is operating, fan speed will be adjusted according to below auto fan speed in SAVE mode;
When compressor stops operation, indoor fan operates at low fan speed.
a. When Tamb. ≥31
℃
, indoor fan operates at super-high fan speed;
b. When 31
℃
>Tamb.≥Tpreset
+
3
℃
, indoor fan operates at high fan speed;
c. When 1
℃
<
Tamb.
<
Tpreset
+
3
℃
, indoor fan operates at medium fan speed;
d. When Tamb.≤1
℃
, indoor fan operates at low fan speed;
As for the switchover among super-high speed, high speed, medium speed and low speed, the unit should operate at every
speed for 3minutes and 3s at least.
④
In this mode, set temperature will be adjusted automatically according to actual operation status.
3 Other Control
(1) Timer Function
General timer and clock timer functions are compatible by equipping remote controller with different functions.
①
General Timer
Timer ON can be set at unit OFF. If selected ON time is reached, the unit will start to operate according to previous setting
status. Time setting range is 0.5-24hr in 30-minute increments.
Timer OFF can be set at unit ON. If selected OFF time is reached, the unit will stop operation. Time setting range is 0.5-24hr in
30-minute increments.
②
Clock Timer (it’s optional for the remote controller with clock timer)
Timer ON
If timer ON is set during operation of the unit, the unit will continue to operate. If timer ON is set at unit OFF, upon ON time
reaches the unit will start to operate according to previous setting status.
Timer OFF
If timer OFF is set at unit OFF, the system will keep standby status. If timer OFF is set at unit ON, upon OFF time reaches the
unit will stop operation.
Summary of Contents for EXH09HL1W
Page 2: ...2010 10 ADL 2 62 599 73 60 74 ...
Page 5: ...210 10 ADL 5 62 599 75 60 77 2 ESD Requirements ...
Page 6: ...210 10 ADL 6 62 599 75 60 77 ...
Page 13: ...210 10 ADL 13 62 599 75 60 77 EXH09HL1W outdoor EXH12HL1W outdoor ...
Page 28: ...210 10 ADL 28 62 599 75 60 77 BOTTOM VIEW ...
Page 37: ...210 10 ADL 37 62 599 75 60 77 H6 Malfunction Flowchart ...