Electro Industries/GaugeTech
Doc # E151701
8-2
Q
A single meter cannot measure the losses in a transformer or transmission line directly. It can
however, include computational corrections to calculate the losses and add or subtract those losses to
the power flow measured at the meter location. This is the method used for loss compensation in the
Nexus® meter.
Q
The computational corrections used for transformer and transmission line loss compensation are
similar. Generically, no-load losses and full-load losses are evaluated and a correction factor for each
loss level is calculated. However, the calculation of the correction factors that must be programmed
into the meter differ for the two different applications. For this reason, the two methodologies will be
treated separately in this chapter.
Q
In the Nexus® meter, Loss Compensation is a technique that computationally accounts for active and
reactive power losses. The meter calculations are based on the formulas below. These equations
describe the amount of active (Watts) and reactive (VARs) power lost due to both iron and copper
effects (reflected to the secondary of the instrument transformers).
Total Secondary Watt Loss =
(((Measured Voltage/Cal point Voltage)
2
x %LWFE) + ((Measured Current/Cal Point Current)
2
x %LWCU)) x Full-scale Secondary VA
Total Secondary VAR Loss =
(((Measured Voltage/Cal point Voltage)
4
x %LVFE) + ((Measured Current/Cal Point Current)
2
x %LVCU)) x Full-scale Secondary VA
Q
The Values for %LWFE, %LWCU, %LVFE, %LVCU are derived from the transformer and meter
information, as demonstrated in following sections.
Q
The calculated loss compensation values are added to or subtracted from the measured Watts and
VARs. The selection of adding or subtracting losses is made through the meter profile when
programming the meter. The meter uses the combination of the add/subtract setting and the
directional definition of power flow (also in the profile) to determine how to handle the losses.
Losses will be "added to" or "subtracted from" (depending on whether add or subtract is selected)
the Received Power flow. For example, if losses are set to "Add to" and received power equals 2000
kW and losses are equal to 20kW then the total metered value with loss compensation would be
2020 kW; for these same settings if the meter measured 2000 kW of delivered power the total
metered value with loss compensation would be 1980 kW.
Q
Since transformer loss compensation is the more common loss compensation method, the meter has
been designed for this application. Line loss compensation is calculated in the meter using the same
terms but the percent values are calculated by a different methodology as described in a subsequent
section below.
Q
Nexus® 1262/1272 Meter Transformer Loss Compensation:
•
Performs calculations on each phase of the meter for every measurement taken. Unbalanced
loads are accurately handled.
•
Calculates numerically, eliminating the environmental affects that cause inaccuracies in
electromechanical compensators.
Summary of Contents for Nexus 1262
Page 1: ... The Leader in Power Monitoring and Control The Leader in Power Monitoring and Control ...
Page 2: ......
Page 4: ...Electro Industries GaugeTech Doc E151701 ...
Page 8: ...e Electro Industries GaugeTech Doc E151701 iv ...
Page 52: ...e Electro Industries GaugeTech Doc E151701 4 8 ...
Page 130: ...Electro Industries GaugeTech Doc E151701 10 14 ...
Page 133: ...Electro Industries GaugeTech Doc E151701 11 3 Fig 11 1 Form 9S Wye no PTs 3 CTs ...
Page 134: ...Fig 11 2 Form 9S Wye 3 PTs 3 CTs Electro Industries GaugeTech Doc E151701 11 4 ...
Page 135: ...Electro Industries GaugeTech Doc E151701 11 5 Fig 11 3 Form 9S 4 Wire Delta no PTs 3 CTs ...
Page 136: ...Fig 11 4 Form 9S 4 Wire Delta 3 PTs 3 CTs Electro Industries GaugeTech Doc E151701 11 6 ...
Page 139: ...Fig 11 7 Form 9S 3 Wire Delta no PTs 2 CTs Electro Industries GaugeTech Doc E151701 11 9 ...
Page 140: ...Fig 11 8 Form 9S 3 Wire Delta 2 PTs 2 CTs Electro Industries GaugeTech Doc E151701 11 10 ...
Page 141: ...Fig 11 9 Form 36S 2 5 Element Wye no PTs 3 CTs Electro Industries GaugeTech Doc E151701 11 11 ...
Page 142: ...Fig 11 10 Form 36S 2 5 Element Wye 2 PTs 3 CTs Electro Industries GaugeTech Doc E151701 11 12 ...
Page 143: ...Fig 11 11 Form 45S Wye no PTs 3 CTs Electro Industries GaugeTech Doc E151701 11 13 ...
Page 144: ...Fig 11 12 Form 45S Wye 2 PTs 3 CTs Electro Industries GaugeTech Doc E151701 11 14 ...
Page 145: ...Fig 11 13 Form 45S 3 Wire Delta no PTs 2 CTs Electro Industries GaugeTech Doc E151701 11 15 ...
Page 146: ...Fig 11 14 Form 45S 3 Wire Delta 2 PTs 2 CTs Electro Industries GaugeTech Doc E151701 11 16 ...
Page 150: ...Electro Industries GaugeTech Doc E151701 11 20 ...
Page 154: ...Electro Industries GaugeTech Doc E151701 12 4 Fig 12 5 Switchboard Meter Side View ...
Page 168: ...Electro Industries GaugeTech Doc E151701 12 18 ...
Page 176: ...Electro Industries GaugeTech Doc E151701 13 8 ...
Page 186: ...Electro Industries GaugeTech Doc E151701 A 2 ...
Page 187: ...Electro Industries GaugeTech Doc E151701 A 3 ...
Page 188: ...Electro Industries GaugeTech Doc E151701 A 4 ...
Page 189: ...Electro Industries GaugeTech Doc E151701 A 5 ...
Page 190: ...Electro Industries GaugeTech Doc E151701 A 6 ...
Page 206: ...Electro Industries GaugeTech Doc E151701 C 14 ...