C
.2: Power, Energy and Demand
Q
It is quite common to exchange power, energy and demand without differentiating between the
three. Because this practice can lead to confusion, the differences between these three
measurements will be discussed.
Q
Power is an instantaneous reading. The power reading provided by a meter is the present flow of
watts. Power is measured immediately just like current. In many digital meters, the power value is
actually measured and calculated over a one second interval because it takes some amount of time to
calculate the RMS values of voltage and current. But this time interval is kept small to preserve the
instantaneous nature of power.
Q
Energy is always based on some time increment; it is the integration of power over a defined time
increment. Energy is an important value because almost all electric bills are based, in part, on the
amount of energy used.
Q
Typically, electrical energy is measured in units of kilowatt-hours (kWh). A kilowatt-hour
represents a constant load of one thousand watts (one kilowatt) for one hour. Stated another way, if
the power delivered (instantaneous watts) is measured as 1,000 watts and the load was served for a
one hour time interval then the load would have absorbed one kilowatt-hour of energy. A different
load may have a constant power requirement of 4,000 watts. If the load were served for one hour it
would absorb four kWh. If the load were served for 15 minutes it would absorb 1⁄4 of that total or
one kWh.
Q
Figure C.7 shows a graph of power and the resulting energy that would be transmitted as a result of
the illustrated power values. For this illustration, it is assumed that the power level is held constant
for each minute when a measurement is taken. Each bar in the graph will represent the power load
for the one-minute increment of time. In real life the power value moves almost constantly.
Q
The data from Figure C.7 is reproduced in Table 2 to illustrate the calculation of energy. Since the
time increment of the measurement is one minute and since we specified that the load is constant
over that minute, we can convert the power reading to an equivalent consumed energy reading by
multiplying the power reading times 1/60 (converting the time base from minutes to hours).
Electro Industries/GaugeTech
Doc # E151701
C
-6
Time (minutes)
Æ
Kilowatts
20
40
60
80
100
Figure .7: Power use over time
Figure C.7: Power Use Over Time
Summary of Contents for Nexus 1262
Page 1: ... The Leader in Power Monitoring and Control The Leader in Power Monitoring and Control ...
Page 2: ......
Page 4: ...Electro Industries GaugeTech Doc E151701 ...
Page 8: ...e Electro Industries GaugeTech Doc E151701 iv ...
Page 52: ...e Electro Industries GaugeTech Doc E151701 4 8 ...
Page 130: ...Electro Industries GaugeTech Doc E151701 10 14 ...
Page 133: ...Electro Industries GaugeTech Doc E151701 11 3 Fig 11 1 Form 9S Wye no PTs 3 CTs ...
Page 134: ...Fig 11 2 Form 9S Wye 3 PTs 3 CTs Electro Industries GaugeTech Doc E151701 11 4 ...
Page 135: ...Electro Industries GaugeTech Doc E151701 11 5 Fig 11 3 Form 9S 4 Wire Delta no PTs 3 CTs ...
Page 136: ...Fig 11 4 Form 9S 4 Wire Delta 3 PTs 3 CTs Electro Industries GaugeTech Doc E151701 11 6 ...
Page 139: ...Fig 11 7 Form 9S 3 Wire Delta no PTs 2 CTs Electro Industries GaugeTech Doc E151701 11 9 ...
Page 140: ...Fig 11 8 Form 9S 3 Wire Delta 2 PTs 2 CTs Electro Industries GaugeTech Doc E151701 11 10 ...
Page 141: ...Fig 11 9 Form 36S 2 5 Element Wye no PTs 3 CTs Electro Industries GaugeTech Doc E151701 11 11 ...
Page 142: ...Fig 11 10 Form 36S 2 5 Element Wye 2 PTs 3 CTs Electro Industries GaugeTech Doc E151701 11 12 ...
Page 143: ...Fig 11 11 Form 45S Wye no PTs 3 CTs Electro Industries GaugeTech Doc E151701 11 13 ...
Page 144: ...Fig 11 12 Form 45S Wye 2 PTs 3 CTs Electro Industries GaugeTech Doc E151701 11 14 ...
Page 145: ...Fig 11 13 Form 45S 3 Wire Delta no PTs 2 CTs Electro Industries GaugeTech Doc E151701 11 15 ...
Page 146: ...Fig 11 14 Form 45S 3 Wire Delta 2 PTs 2 CTs Electro Industries GaugeTech Doc E151701 11 16 ...
Page 150: ...Electro Industries GaugeTech Doc E151701 11 20 ...
Page 154: ...Electro Industries GaugeTech Doc E151701 12 4 Fig 12 5 Switchboard Meter Side View ...
Page 168: ...Electro Industries GaugeTech Doc E151701 12 18 ...
Page 176: ...Electro Industries GaugeTech Doc E151701 13 8 ...
Page 186: ...Electro Industries GaugeTech Doc E151701 A 2 ...
Page 187: ...Electro Industries GaugeTech Doc E151701 A 3 ...
Page 188: ...Electro Industries GaugeTech Doc E151701 A 4 ...
Page 189: ...Electro Industries GaugeTech Doc E151701 A 5 ...
Page 190: ...Electro Industries GaugeTech Doc E151701 A 6 ...
Page 206: ...Electro Industries GaugeTech Doc E151701 C 14 ...