D: DNP 3.0 Protocol Assignments
Electro
Industries/GaugeTech
™
Powered by Innovation™
Maximum Demands of Total Power (Points 15 - 19)
These points are formatted as 2's complement fractions. They represent a fraction of
4500W Secondary in normal operation, or 3000W Secondary in Open Delta operation.
Inputs above/below +/-4500 or +/-3000W Secondary are pinned at +/-4500 or +/-
3000W Secondary, respectively.
Phase Angle (Points 20 - 25)
These points are formatted as 2's complement integers. They represent angles from -
180.00 (0x0F8F8) to +180.00 (0x00708).
CT & PT Ratios (Points 26 - 31)
Point
Reading
15
Maximum Positive Demand Total Watts
16
Maximum Positive Demand Total VARs
17
Maximum Negative Demand Total Watts
18
Maximum Negative Demand Total VARs
19
Maximum Average Demand VAs
Point
Reading
20
Phase A Current Angle
21
Phase B Current Angle
22
Phase C Current Angle
23
Volts A-B Angle
24
Volts B-C Angle
25
Volts C-A Angle
Point
Reading
26
CT Ratio Numerator
27
CT Ratio Multiplier
28
CT Ratio Denominator
29
PT Ratio Numerator
30
PT Ratio Multiplier
31
PT Ratio Denominator