6: Using the Shark® 100 Meter
Electro
Industries/GaugeTech
™
Powered by Innovation™
Example
: High Set Point = 110% (Out of Limit at 132V);Return Hysteresis =
105%(Stay Out until 126V)
Low Set Point: % of Full Scale
Return Hysteresis: Point to go back in Limit.
Your settings appear in the Table at the bottom of the screen
NOTES:
If Return Hysteresis is > High Set Point, the Limit is Disabled.
IMPORTANT!
When you have finished making changes to the Device Profile, click
Update Device
to send the new Profile settings to the meter.
NOTE:
Refer to Chapter 9 of the
CommunicatorPQA®, MeterManagerPQA®, and
EnergyPQA.com
TM
Software User Manual
for additional instructions on configuring the
Shark® 100/50 transducer/meter settings.