Doc
#
E145701
6-27
6: Using the Shark® 100 Meter
Electro
Industries/GaugeTech
™
Powered by Innovation™
PT Denominator (Secondary): 40 - 600
PT Multiplier: 1, 10, 100, or 1000
Voltage Full Scale: Calculations based on selections. Click
Recalculate
to see the
result of changes.
System Wiring
3 Element Wye; 2.5 Element Wye; 2 CT Delta
Phases Displayed
A, AB, or ABC
NOTE:
Voltage Full Scale = PT Numerator x PT Multiplier
Example:
A 14400/120 PT would be entered as:
PT Numerator: 1440
PT Denominator: 120
Multiplier: 10
This example would display a 14.40kV.
Example CT Settings:
200/5 amps: Set the Ct-n value for 200, Ct-Multiplier value for 1
800/5 amps: Set the Ct-n value for 800, Ct-Multiplier value for 1
2,000/5 amps: Set the Ct-n value for 2000, Ct-Multiplier value for 1
10,000/5 amps: Set the Ct-n value for 1000, Ct-Multiplier value for 10
Example PT Settings:
277/277 volts: Pt-n value is 277, Pt-d value is 277, Pt-Multiplier is 1
14,400/120 volts: Pt-n value is 1440, Pt-d value is 120, Pt-Multiplier value is 10
138,000/69 volts: Pt-n value is 1380, Pt-d value is 69, Pt-Multiplier value is 100