9.4: Factory Settings and Reset Button
9.4: Factory Settings and Reset Button
n
Factory Settings:
All Nexus I/O Modules are shipped with a preset address and a baud rate of 57600.
n
Reset Button
:
If there is a communication problem or if you are unsure of a module’s address and baud rate, press
and hold the RESET button for 3 seconds; the module will reset to a default address of
247 at 57600
baud for 30-seconds
. This will enable you to interrogate the I/O using the Nexus Communicator
software; see the
Nexus Communicator User Manual
.
Model #
Module
Factory-Set Address
1mAON4
0–1mA, 4-Channel Analog Output
128
1mAON8
0–1mA, 8-Channel Analog Output
128
20mAON4
4–20mA, 4-Channel Analog Output
132
20mAON8
4–20mA, 8-Channel Analog Output
132
8AI1
0–1mA, 8-Channel Analog Input
136
8AI2
0–20mA, 8-Channel Analog Input
140
8AI3
0–5 VDC, 8-Channel Analog Input
144
8AI4
0–10 VDC, 8-Channel Analog Input
148
4RO1
4 Latching Relay Outputs
156
4PO1
4 KYZ Pulse Outputs
160
8DI1
8 Digital Status Inputs (Wet/Dry)
164
4RTD1
4 RTD Inputs
168
Summary of Contents for Nexus 1250
Page 2: ...e Electro Industries GaugeTech Doc E107 7 06 121 Courtesy of NationalSwitchgear com ...
Page 6: ...E Electro Industries GaugeTech Doc E107 7 06 121 iv Courtesy of NationalSwitchgear com ...
Page 12: ...e Electro Industries GaugeTech Doc E107 7 06 121 x Courtesy of NationalSwitchgear com ...
Page 26: ...e Electro Industries GaugeTech Doc E107 7 06 121 2 10 Courtesy of NationalSwitchgear com ...
Page 34: ...e Electro Industries GaugeTech Doc E107 7 06 121 3 8 Courtesy of NationalSwitchgear com ...