e
Electro Industries/GaugeTech
Doc #: E107-7-06-121
9-3
Mounting Bracket
Male RS-485
Side Port
Female RS-485
Side Port
LEDs
I/O Port (Size and pin configuration vary)
Reset Button
9.3: Using Multiple I/O Modules
9.3: Using Multiple I/O Modules
n
Each I/O module in a group
must be assigned a unique address
. See the
Nexus Communicator
User Manual
for details on configuring and programming the I/O Modules.
n
Use the male and female RS-485 side ports to attach I/O modules together. Screw the modules
together, using the integrated fastening system. Attach the mounting brackets to each side of the
group to ensure all modules are securely connected.
Figure 9.3: Multiple I/Os
Nexus 1250
I/Os must use the Nexus Monitor’s Port 4.
Set the port to 57600 Baud, Master.
RS-485 Cable
Addr
160
Addr
128
Addr
156
Group of 3 I/Os