The Nexus Monitor supplies power to up to four connected modules. See section 9.2 for power and
communication details. See sections 5.12 and 5.13 for the steps to determine if you must use an
additional power source.
n
The figure on the next page shows the configuration of the Digital Status Input Module’s I/O Port,
which is used for connection to an interface device. This module is used for either additional
status
detect
or for
accumulating pulses from external equipment
, such as power meters, water meters,
etc. A user programmable address and functionality afford versatility.
9.9: Digital Status Input Module
9.9: Digital Status Input Module
Digital Status Input Module Specifications
Model Number
Communication
Power
Operating Temperature
Voltage Rating
Detection
Factory Settings
Default Settings
(Reset Button)
8DI1
RS-485, Modbus RTU
Programmable Baud Rates from 4800 to 57600 Baud
15–20 VDC at 50–200 mA; Nexus Monitor will support
up to four modules.
-20°C to 70°C / -4°F to +158°F
Up to 300 VDC
Wet/Dry, Auto Detect
Modbus Address: 164
Baud Rate: 57600
Delay: 0
Modbus Address: 247
Baud Rate: 57600
Summary of Contents for Nexus 1250
Page 2: ...e Electro Industries GaugeTech Doc E107 7 06 121 Courtesy of NationalSwitchgear com ...
Page 6: ...E Electro Industries GaugeTech Doc E107 7 06 121 iv Courtesy of NationalSwitchgear com ...
Page 12: ...e Electro Industries GaugeTech Doc E107 7 06 121 x Courtesy of NationalSwitchgear com ...
Page 26: ...e Electro Industries GaugeTech Doc E107 7 06 121 2 10 Courtesy of NationalSwitchgear com ...
Page 34: ...e Electro Industries GaugeTech Doc E107 7 06 121 3 8 Courtesy of NationalSwitchgear com ...