Doc #: E107-6-07-121
7-8
Losses Due to Copper
Losses Due to Copper
KVA Load Losses
= (Impedance) x (Bank KVA Rating)
KW
= _________ x _______________
Load Loss Vars
= SQRT((Load VA Losses)
2
- (Load Watt Losses)
2
)
= SQRT((______________)
2
- (________________)
2
)
It (Primary) at Rated Bank KVA and Test Phase Voltage
= (Bank KVA Rating/Test Voltage,Phase to Phase) x SQRT (3)
= (_______________/__________________) x SQRT (3)
Adjust Load Losses due to current to the Nexus Monitor Secondary Current:
Watt Losses (CU)
= ((5 x CTR)/It (Primary)
2
x Load Loss Watts
KW
= ((5 x ___)/___________)
2
x _______________
Var Losses (CU)
= ((5 x CTR)/It (Primary)
2
x Load Loss Vars
KVA
= ((5 x ___)/___________))
2
x _______________
PERCENT COMPENSATION FACTORS
Nominal Primary KVA = (120V x VTR) x (5A x CTR ) x 3
KVA
= (120V x _____) x (5A x _____) x 3
%LWFE
=
(Watt Losses (FE) (KW) x 100)/Nominal Primary KVA
%
=
(_____________________ x 100)/____________
%LVFE
=
(VAR Losses (FE) (KW) x 100)/Nominal Primary KVA
%
=
(_____________________ x 100)/____________
%LWCU
=
(Watt Losses (CU) (KW) x 100)/Nominal Primary KVA
%
=
(_____________________ x 100)/____________
%LVCU
=
(VAR Losses (CU) (KW) x 100)/Nominal Primary KVA
%
=
(_____________________ x 100)/____________
Summary of Contents for Nexus 1250
Page 2: ...e Electro Industries GaugeTech Doc E107 7 06 121 Courtesy of NationalSwitchgear com ...
Page 6: ...E Electro Industries GaugeTech Doc E107 7 06 121 iv Courtesy of NationalSwitchgear com ...
Page 12: ...e Electro Industries GaugeTech Doc E107 7 06 121 x Courtesy of NationalSwitchgear com ...
Page 26: ...e Electro Industries GaugeTech Doc E107 7 06 121 2 10 Courtesy of NationalSwitchgear com ...
Page 34: ...e Electro Industries GaugeTech Doc E107 7 06 121 3 8 Courtesy of NationalSwitchgear com ...