e
Electro Industries/GaugeTech
Doc #: E107-7-06-121
4-3
n
Do not ground the unit through the negative of the DC supply. Separate grounding is required.
n
Externally fuse the power supply with a 5 Amp fuse.
Control Power
Option Suffix
18–60 Volts DC
D
90–276 Volts AC/DC
D2
4.8: Wiring Diagrams
4.8: Wiring Diagrams
Choose the diagram that best suits your application. Diagrams appear on the following pages. If the
connection diagram you need is not listed, contact EIG for a custom connection diagram.
Note
: If you purchased a “G” Option Nexus for a 300 Volt secondary, be sure to enable the option in the
CT and PT section of the Nexus Communicator software’s Device Profile (see the
Nexus Communicator
User Manual
for details).
Figure #
Description
4.1
4.2
4.3
4.4
4.5
4.6
4-Wire Wye, 3-Element Direct Voltage with 4 CTs
4-Wire Wye, 3-Element with 3 PTs and 4 CTs
3-Wire, 2-Element Open Delta with 2 PTs and 3 CTs
3-Wire, 2-Element Open Delta with 2 PTs and 2 CTs
3-Wire, 2-Element Delta Direct Voltage with 3 CTs
3-Phase, 4-Wire Wye, 2.5 Element with 2 PTs and 3 CTs
4.7
4-Wire, 3-Element Grounded Delta with 4 CTs
Summary of Contents for Nexus 1250
Page 2: ...e Electro Industries GaugeTech Doc E107 7 06 121 Courtesy of NationalSwitchgear com ...
Page 6: ...E Electro Industries GaugeTech Doc E107 7 06 121 iv Courtesy of NationalSwitchgear com ...
Page 12: ...e Electro Industries GaugeTech Doc E107 7 06 121 x Courtesy of NationalSwitchgear com ...
Page 26: ...e Electro Industries GaugeTech Doc E107 7 06 121 2 10 Courtesy of NationalSwitchgear com ...
Page 34: ...e Electro Industries GaugeTech Doc E107 7 06 121 3 8 Courtesy of NationalSwitchgear com ...