![Electro Industries/GaugeTech Nexus 1250 Installation & Operation Manual Download Page 56](http://html.mh-extra.com/html/electro-industries-gaugetech/nexus-1250/nexus-1250_installation-and-operation-manual_2379729056.webp)
e
Electro Industries/GaugeTech
Doc #: E107-7-06-121
5-12
Nexus P60N Display, Back View (Detail)
Top
Bottom
5.9: RS-485 Connection
5.9: RS-485 Connection—
—Nexus Monitor to the Nexus P60N External Display
Nexus Monitor to the Nexus P60N External Display
n
To connect the Nexus P60N Touch Screen External Display, use the Stand Alone Interface Cable
provided with the display. The cable is six (6) feet long with 20 AWG conductors (see detail
below). Insert one end of the supplied cable into port 3 of the Nexus Monitor. Port 3 is factory-set
to match the Nexus Display’s baud rate of 9600. To use a port other than port 3, you must set the
port’s baud rate to 9600 using the Nexus Communicator software (see the
Nexus Communicator
User Manual
). Insert the other end of the cable into the back of the Nexus P60N Display. The
connectors fit only one way into the ports.
Stand Alone Interface Cable
Nexus P60N Display Port
Figure 5.11: Nexus Monitor Connected to Nexus P60N Touch Screen Display
P60N Connection Color Key
LCD
Nexus
Color
Pattern
5 DCIN
(12-30VDC)
4 (GND)
V+
Red
V-
Black
3 (485+)
A(+)
White
2 (485-)
B(-)
Black
1 (GND)
S
Silver
Nexus Monitor Port 3
Factory Test
Connector
Summary of Contents for Nexus 1250
Page 2: ...e Electro Industries GaugeTech Doc E107 7 06 121 Courtesy of NationalSwitchgear com ...
Page 6: ...E Electro Industries GaugeTech Doc E107 7 06 121 iv Courtesy of NationalSwitchgear com ...
Page 12: ...e Electro Industries GaugeTech Doc E107 7 06 121 x Courtesy of NationalSwitchgear com ...
Page 26: ...e Electro Industries GaugeTech Doc E107 7 06 121 2 10 Courtesy of NationalSwitchgear com ...
Page 34: ...e Electro Industries GaugeTech Doc E107 7 06 121 3 8 Courtesy of NationalSwitchgear com ...