5-9
5.4: RS-485 Connection
5.4: RS-485 Connection—
—Nexus Monitor to a Computer or PLC
Nexus Monitor to a Computer or PLC
n
Use any Port on the Nexus. If you use Port 1, set the selector switch beneath the port to RS-485 (see
Figure 5.3).
n
The link using RS-485 is capable for up to 4000 feet (1219 meters).
n
You
must
use an RS-485 to RS-232 converter, such as EIG’s Unicom 2500. See section 5.5.
n
For information on connecting the Nexus Monitor to a modem, see sections 5.14–5.16.
n
Do not use the V(+)/V(-) pins; they supply power to the Nexus Displays and Nexus I/O Modules.
5.5: RJ-11 (Telephone Line) Connection
5.5: RJ-11 (Telephone Line) Connection—
—Nexus with Internal Modem Option
Nexus with Internal Modem Option
to a PC
to a PC
n
Use RJ-11 Standard Telephone Line to connect with the Nexus. The RJ-11 line is inserted into the
RJ-11 Port on the face of the Nexus with Internal Modem Option.
n
The length of the connection using RJ-11 into the Nexus is virtually unlimited.
n
To connect with other Nexus Monitors in either local or remote locations, you MUST use Port 2 as a
Master and an RS-485 connection.
n
The link using RS-485 is capable for up to 4000 feet (1219 meters).
n
For more information on the Nexus Monitor with the Internal Modem Option, see
Chapter 10
of this
manual.
5.6: RJ-45 Connection
5.6: RJ-45 Connection—
—Nexus with Internal Network Option to multiple PC’s
Nexus with Internal Network Option to multiple PC’s
n
The Internal Network Option conforms to the IEEE 802.3, 10BaseT specification using unshielded
twisted pair (UTP) wiring. This allows the use of inexpensive RJ-45 connectors and CAT 3 or better
cabling.
n
Using this LAN connection allows multiple PC’s to be connected concurrently. The RJ-45 line is
inserted into the RJ-45 Port on the face of the Nexus with Internal Network Option.
n
The connection using RJ-45 into the Nexus can connect the Nexus to a network using Modbus/TCP
protocol over Ethernet.
n
To connect with other Nexus Monitors in either local or remote locations, you MUST use Port 2
(which is labeled Ethernet Gateway) as a Master and an RS-485 connection. The link using RS-485
is capable for up to 4000 feet (1219 meters).
n
For more information on the Nexus Monitor with the Internal Network Option, see
Chapter 11
of
this manual.
Summary of Contents for Nexus 1250
Page 2: ...e Electro Industries GaugeTech Doc E107 7 06 121 Courtesy of NationalSwitchgear com ...
Page 6: ...E Electro Industries GaugeTech Doc E107 7 06 121 iv Courtesy of NationalSwitchgear com ...
Page 12: ...e Electro Industries GaugeTech Doc E107 7 06 121 x Courtesy of NationalSwitchgear com ...
Page 26: ...e Electro Industries GaugeTech Doc E107 7 06 121 2 10 Courtesy of NationalSwitchgear com ...
Page 34: ...e Electro Industries GaugeTech Doc E107 7 06 121 3 8 Courtesy of NationalSwitchgear com ...