USV: OFFICE 400 - 2000
Zubehör
Serie
OFFICE
42
13.
Technical Data
OFFICE:
400
400 VA, 240 W
600
600 VA, 360 W
800
800 VA, 480 W
UP
S
I
n
p
u
t
Network
1 Phase, neutral conductor and PE conductor
Nominal Voltage
230
VAC
Voltage Range
170 - 280
VAC
Frequency Range
46 Hz
– 54 Hz (
50
Hz)
U
P
S
Ou
tp
u
t
Network
1 Phases, neutral conductor and PE conductor
Nominal Voltage
230
VAC
Voltage Accuracy
10 %
(Inverter mode)
AVR (Boost)
+10%
(Mains operation mode)
AVR (Buck)
-10%
(Mains operation mode)
Frequency
50Hz
1 %
(Inverter mode)
Wave Form
Sine
Switchover Time
typical
4-6
ms, maximal 10 ms
B
a
tt
e
ry
B
ank
Voltage
12
VDC
Capacity
1x
4.5 Ah
1x
7 Ah
1x
9 Ah
Charging Time
12 h
(80 % of capacity reached)
Device
Device Protection
Overload, Deep Discharge, Overcharge
Overvoltage Protection
Protection of a data line RJ11, (not with the RS variant)
Dimensions
300 x 101 x 142
mm (D x W x H)
Weight
3.7 kg
4.4 kg
5.0 kg
Device Class
Class 2
Communication
USB, RS232 (RS variant), MegaTec Protocol
Standards / Guidelines
Safety: EN 62040-1
EMC:
EN 62040-2
Service:
EN 62040-3
E
n
vir
o
n
m
e
n
t
Temperature Ranges
Operation:
0 ... 40 °C
Recommended *: 15
… 25°C
Storage: -25 ... 55 °C (without accumulators)
Storage: 0 ... 40 °C (with accumulators)
Rel. Humidity
0
– 90 % (not condensing)
Noise Level
< 40 dB (without fan)